Heater Burnout Detection Doesn’t Work Properly
Possible cause
Remedy
Reference
Current Transformer is not connected properly.
Correctly wire Current Transformer.
Sec. 3-5
E54-CT2 is being used.
Only E54-CT1 and E54-CT3 can be used as Current
Transformers.
Sec. 1-4-3,
App. A
HB and HS alarms have not been made op-
erational.
Use Alarm Point Write (WU) to make alarms operational.
Sec. 4-2-7
Setting for heater burnout detection level is
0.0 A.
With a setting of 0.0 A the HB alarm is invalid. Make the
proper setting.
Sec. 4-2-28
Setting for heater burnout detection level is
incorrect.
Take into account variations in measurement and fluctua-
tions in heater power supply voltage. Allow for a 1 A fluc-
tuation due to ambient temperature influences.
Sec. 1-4-3,
3-5-4
HB and HS alarms were made operational be-
fore heater was turned on.
Turn on heater first.
Sec. 1-4-3
Control output is not being used.
HG and HS alarms are synchronous with control output,
so control output must be used.
Sec. 3-5-4
Operation is not starting.
Start operation with OS command.
Sec. 3-5
Control output was ON for less than 200 ms.
HB alarm detection will not operate unless control output
stays ON for 200 ms.
Sec. 3-5
Control output was OFF for less than 200 ms.
HB alarm detection will not operate unless control output
stays OFF for 200 ms.
Sec. 3-5
Heater current exceeds 50 A.
To avoid damage, do not run a current of over 50 A.
App. A
Heater’s rated current and actual current differ.
Use Heater Current Read to check actual heater current,
and set detection level accordingly.
Sec. 4-2-30
Troubleshooting Lists
Section 6-1
Summary of Contents for E5ZD
Page 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Page 2: ......
Page 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 8: ......
Page 10: ......
Page 18: ......
Page 76: ......
Page 128: ......
Page 132: ......
Page 142: ......
Page 146: ......
Page 148: ......
Page 150: ......
Page 154: ......
Page 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...