Specifications
Ratings
Supply voltage
100 to 240 VAC, 50/60 Hz (either frequency applicable with same unit)
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC)
Input
Thermocouple (K/J/T/E/R/S/L/U) or platinum resistance thermometer (Pt100/JPt100)
selectable
Potentiometer input
100
Ω
to 2.5 k
Ω
Control output
Relay output: open, close; SPST-NO contacts; 3 A, 250 VAC (resistive load); inrush current: 1
A max.
Control mode
PID control with auto-tuning
Alarm output
Relay output, SPST-NO contacts; 3 A, 250 VAC (resistive load)
Setting method
Digital setting via Up and Down Keys
Indication method
Digital indications (character heights PV: 11 mm and SV: 8 mm) (Color PV: red, SV: green)
Other functions
Upper and lower limits for set value
Key protection
Input shift
Display unit selection (
°
C/
°
F)
Normal and reverse output selection
Valve position display
Motor calibration function
Watchdog timer function (Detects failures in the CPU and restores the CPU.)
Manual output (balanceless-bumpless operation switchable)