E5EX-P
E5EX-P
6
Alarm Mode Selector (SW205: ALM)
Alarm mode selector is provided for all E5AX Temperature Controllers. Ten alarm modes, listed in the following table, can be selected using this
switch. The switch is factory-set to position 2, i.e., the upper-limit alarm mode.
Switch
Mode (SW205)
Alarm output
Setting range
setting
Alarm operation
Display
When X is positive
When X is negative
0
No alarm
No display
OFF
---
1
Upper- and lower-limit
alarm
)--(
X
X
---
Thermocouple: 0
°
to 9,999
°
C/
°
F
Platinum resistance thermometer:
0
°
to 999.9
°
C/
°
F
2
Upper-limit alarm
---(
X
X
Thermocouple: –999
°
to
9,999
°
C/
°
F
3
Lower-limit alarm
)---
X
X
Platinum resistance thermome-
ter: –99.9
°
to 999.9
°
C/
°
F
4
Upper- and lower-limit
range alarm
-()-
X
X
---
Thermocouple: 0
°
to 9,999
°
C/
°
F
5
Upper- and lower-limit
alarm with standby se-
quence
3--e
X
X
---
Platinum resistance thermometer:
0
°
to 999.9
°
C/
°
F
6
Upper-limit alarm with
standby sequence
---e
X
X
Thermocouple: –999
°
to
9,999
°
C/
°
F
7
Lower-limit alarm with
standby sequence
3---
X
X
Platinum resistance thermome-
ter: –99.9
°
to 999.9
°
C/
°
F
8
Absolute-value alarm
1--(
Y
0
°
C
Y
0
°
C
Key Protection Switch (SW101, PROTECT)
When the key protection switch is set to the ON position, the Level Key, Up and Down Keys, and Auto-tuning Key cannot be operated. In effect,
the Temperature Controller is write-protected and the set values (such as the alarm value) can be read out only. The set point, however, will not
be protected if the SP protection disable is turned ON (pin 4 of SW201).