8
Temperature Controllers
E5CSZ
2. Operation Settings
Use the control mode switches (
) to change the
control mode. (All switches are OFF for the default settings.)
3. Alarm Modes
Select the number of the alarm mode switch
when changing
the alarm mode. (The default is 2).
Note: 1. No alarm. The alarm value (alarm operation display) will not
be displayed when the setting is 0 or 9 even if the selection
key is pressed.
Alarm Setting Range
X: 0 to FS (full scale); Y: Within temperature range
The value of X is the deviation setting for the SP (set point).
2. Standby Sequence Function (The standby sequence
operates when the power is turned ON.)
For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 6.
Function selection
1
2
3
4
5
6
ON/OFF
PID
PID control
ON
ON/OFF control
OFF
Control
period
2 s
ON
20 s
OFF
Direct/
reverse
opera-
tion
Direct operation
(cooling)
ON
Reverse operation
(heating)
OFF
Input
shift
display
Enabled
ON
Disabled
OFF
Tempera-
ture
Sensor
selection
Multi-input
(thermo-
couple/
platinum
resistance
thermome-
ter)
Platinum
resis-
tance
thermom-
eter
input
ON
Thermo-
couple
input
OFF
Temper-
ature
unit
°
F
ON
°
C
OFF
6
5
4
3
2
1
ON
6
5
4
3
2
1
ON
Set
value
Alarm type
Alarm output operation
0, 9
Alarm function OFF
OFF
1
Upper- and lower-
limit
2
Upper-limit
3
Lower-limit
4
Upper- and lower-
limit range
5
Upper- and lower-
limit with standby
sequence (See note
2.)
6
Upper-limit with
standby sequence
(See note 2.)
7
Lower-limit with
standby sequence
(See note 2.)
8
Absolute-value
upper-limit
0 1
2
3
45
6
7
8
9
X
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
0
Y
ON
OFF
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm
output
ON
OFF
Upper-limit
alarm
SP
Lower-limit
alarm
Alarm
output
ON
OFF
Rising Temperature
Dropping Temperature
Note: Turn OFF the power before changing the DIP switch settings on the E5CSZ. Each of the switch settings will be enabled after the power is
turned ON.