Temperature Controllers
E5CSZ
15
Alarm Mode Switch (Alarm Model Only)
Temperature Range Switch
Previous model
E5CSZ
Function Selection
4
Alarm
Modes
Lower-limit
ON
Upper-limit
OFF
X
SP
ON
OFF
SP
X
ON
OFF
0 1
2
3
45
6
7
8
9
Set
value
Alarm type
Alarm output operation
0, 9
Alarm function OFF
OFF
1
Upper- and lower-
limit
2
Upper-limit
3
Lower-limit
4
Upper- and lower-
limit range
5
Upper- and lower-
limit with standby
sequence (See note
2.)
6
Upper-limit with
standby sequence
(See note 2.)
7
Lower-limit with
standby sequence
(See note 2.)
8
Absolute-value
upper-limit
X
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
0
Y
ON
OFF
Function selection
5
6
Temperature
Range
KJ
J: 0 to 300
°
C
ON
ON
K: 0 to 999
°
C
OFF
ON
K: 0 to 500
°
C
ON
OFF
K: 0 to 300
°
C
OFF
OFF
P
---
ON
ON
Pt100: 0 to 300
°
C
OFF
ON
Pt100: 0.0 to 99.0
°
C
ON
OFF
Pt100: 0.0 to 50.0
°
C
OFF
OFF
0 1
2
3
45
6
7
8
9
Set
value
Temperature Range
0
Control Mode
Switch 5: OFF
K: 0 to 1,300
°
C/
−
99 to 1,999
°
F
1
K: 0.0 to 199.9
°
C/0.0 to 199.9
°
F
2
J:
−
99 to 850
°
C/
−
99 to 1,500
°
F
3
J: 0.0 to 199.9
°
C/0.0 to 199.9
°
F
4
L:
−
99 to 850
°
C/
−
99 to 1,500
°
F
0
Control Mode
Switch 5: ON
Pt100:
−
99 to 850
°
C/
−
99 to 1,500
°
F
1
Pt100: 0.0 to 199.9
°
C/0.0 to 199.9
°
F
2
Pt100:
−
99 to 99
°
C/
−
99 to 99
°
F
3
Pt100: 0 to 200
°
C/0 to 200
°
F
4
Pt100: 0 to 400
°
C/0 to 400
°
F