Simplicity on the Worksite
Solutions Guide for FAQs: E5
@
N
Using ON/OFF Control
2-3
Using ON/OF
F
Control
You set this parameter in the Adjustment Level. The parameter is set to 1.0
°
C by default.
3
Setting the Hysteresis
Turn ON the power supply.
1
Press the
(Level) Key for less
than 1 second.
Operating Display
Change the parameter with the Key.
2
←
l.adj
(L.ADJ) will be displayed
to show that the Adjustment
Level has been entered.
←
hys
(HYS): Indicates the Hysteresis parameter.
←
Default setting is
1.0
(1.0°C).
Press the (Mode) Key
several times to display
hys
(HYS).
Change the set value with the
(Up
and Down) Keys.
Set the parameter with the Keys.
3
Adjustment Level
Adjustment Level
Adjustment Level
(When finished, press the (Level) Key to return to the
operation display.)