Simplicity on the Worksite
Solutions Guide for FAQs: E5
@
N
Using PID Control
3-4
Using PID Co
n
trol
Executing Autotuning
at
stops flashing, autotuning is finished.
Press the
(Level) Key for
less than 1
second.
Operating Display
Autotuning will be started when
at
(AT)
←
starts flashing.
←
at-2
(AT-2): 100% autotuning executed.
Change the parameter with the Key.
2
Autotuning will start at
at-2
3
4
Adjustment Level
←
l.adj
(L.ADJ) will be displayed to
show that the Adjustment Level
has been entered.
←
at
(AT): Indicates the Autotuning parameter.
←
Default setting is
off
(OFF):
Autotuning stopped.
off
(OFF)
at-2
(At-2)
at-1
(At-1)
: Autotuning stopped (default).
: 100% autotuning executed.
: Refer to page 3-6.
←
at
will stop flashing to indicate that
autotuning is finished.
Use the (Up and Down) Keys to
select
at-2
(AT-2) (100% autotuning).
Press the (Mode) Key
several times to display
at
(AT).
Adjustment Level
Adjustment Level
Adjustment Level
Turn ON the power supply.
1
(When finished, press the (Level) Key to return to the operation display.)
←
SV flashing: Autotuning is being executed.
*You can return to the Operation Level during autotuning execution.
Operating Display
●
After Returning to Operation Level