Simplicity on the Worksite
Solutions Guide for FAQs: E5
@
N
Setting Temperature Alarms
4-8
Setting T
empe
rature Alarms
Setting Alarm Type
1, 4, or 5
(Upper-limit and
Lower-limit Alarms or Upper-limit and Lower-limit
Range Alarms)
Setting Alarm Type
2, 3, 6, 7, 8, 9,10, or
11
(Upper-limit Alarms and Lower-limit
Alarms)
Alarm value: 30°C (example)
←
al1h
(AL1H): Alarm Upper Limit 1
Alarm value: 30°C (example)
←
al-1
(AL-1): Alarm Value 1
Change the set value
with the (Up and
Down) Keys.
Operation Level
Operation Level
Change the set value
with the (Up and
Down) Keys.
Alarm Value 1:
30,
al-1
(AL-1)
Example:
Alarm Value 1 = Upper-limit Alarm: 30°C
Alarm upper limit 1:
30,
al1h
(AL1H)
Alarm ON
ON
SP
Alarm lower limit 1:
20,
al1l
(AL1L)
SP
Alarm ON
ON
Press the (Mode) Key several times to display
al1l
(AL1L).
Alarm value: 20°C (example)
←
al1l
(AL1L): Alarm lower limit 1
Change the set value
with the (Up and
Down) Keys.
Alarm ON
ON
SP
Example:
Alarm Upper Limit 1 = 30°C,
Alarm Lower Limit 1 = 20°C
Set the alarm value with the Keys.
3
(When finished, press the (Mode) Key to return to the operation display.)
If required, use the (Mode) Key and the (Up and Down) Keys to repeat steps 2 and 3 and set the
alarm values for
al-2
(AL-2) (Alarm Value 2,
al-3
(AL-3) (Alarm Value 3),
al2h
(AL2H) (Alarm Upper Limit 2),
al2l
(AL2L) (Alarm Lower Limit 2),
al3h
(AL3H) (Alarm Upper Limit 3), and
al3l
(AL3L) (Alarm Lower Limit 3).
(The number of alarms that is supported depends on the model of Temperature Controller. Some of the alarm
parameters may not be displayed.)