Level 1 Mode
off
a t
0
s p - 0
0
0
0
10.0
p
233
i
d
40
1.00
0.0
c - d b
50.0
h y s
0.10
0.10
s p - 1
a l - 1
a l - 2
c - s c
o f - r
c h y s
20
c p
20
c - c p
Control Period (Cool)
Available when the Controller has a relay or voltage output, or is in advanced PID control in heating and cooling
control.
Range = 1 to 99 s. Default = 20 s.
Control Period (Heat)
Available only when the Controller has a relay or voltage output, or is in advanced PID control.
Range = 1 to 99 s. Default = 20 s.
Hysteresis (Cool
)
Available when the Controller is in ON/OFF control in heating and cooling control.
Range = 0.01 to 99.99 FS. Default = 0.10.
Hysteresis (Heat)
Available when the Controller is in ON/OFF control.
If PID control selected, this value will not appear on the menu.
Range = 0.01 to 99.99 FS. Default = 0.10.
Manual Reset Value
Available ONLY when the integral time parameter of the Controller in standard control is set to
0
.
The Controller must be in Standard or Advanced PID control and self-tune must be set to off.
Dead Band
Used when the Controller is in heating and cooling control. This setting determines the amount of overlap or dead
band present in a heat/cool configuration. Range = -19.99
→
99.99.
Negative values = overlap band. Positive values = Dead band.
Cooling Coefficient
Used when the Controller is in heat/cool control. This setting describes the ratio between the heating proportional
band and the cooling proportional band.
c - s c
=
cooling P band
heating P band
Derivative Time
Range = 0 to 3999 seconds
See Note at right.
Integral Time
Range = 0 to 3999 seconds
Proportional Band
Range = 0.1% to 999.9%
Alarm Value 2
Available only when the alarm output function of the Controller is selected. This setting determines what the Alarm
2 set point will be. This alarm can be programmed to work on Control Output 2 or the SUB-1 output (user-select-
able). Factory Default = Control Output 2.
Note
:
Alarm Value 3 is available only when SUB-1 or Control Output No. 1 is selected as AL-3.
Alarm Value 1
Available only when Control Output 2 is not used as a control output. This setting determines what the Alarm 1 set
point will be.
Set Point 1
Used only with multi-SP function. This set point is active when the Event input is ON.
This parameter is available only if an Event Input Option Board is installed.
Set Point 0
Default set point when used with multi-SP function. This set point is active when the Event input is OFF.
AT Execute/Cancel
Starts the Auto-tune function or cancels an active auto-tune. When an active auto-tune is cancelled, the original
PID constants will be used again.
AT-1 = Limited MV change during Autotuning (
±
40% max.)
AT-2 = Full MV change during Autotuning (
±
100% max.)
Note:
This level 1 Mode ends here for the E5CK models only. For all other E5
K models in this data sheet,
continue with the next page.
Note:
For Valve Positioning Models E5
K–PRR2, all
subsequent parameters (those after Derivative Time)
listed in Level 1 Mode are not available. See Level 1
Valve Positioning model (provided on the following
page).
Note:
E5AK and E5EK can have up to 4 set points or 4 alarms
Note:
E5AK and E5EK can have up to 4 set points or 4 alarms