If the control mode is 2-PID with fuzzy self-tuning, the
parameters
p
,
i
,
d
, or
ofr
will not be displayed (i.e., there is no
need to set these parameters). Fuzzy self-tuning always adjusts
all PID constants to optimum values inside the Temperature
Controller.
Proportional Band:
p
When the character “
p
” is displayed on the PV display, the propor-
tional band (P constant) can be changed using the Up and Down
Keys. The new value will be displayed on the SV display. It can be
set in a range from 0.1
°
to 999.9
°
C/
°
F in units of 0.1
°
C/
°
F. The value
is factory-set to 8.0
°
C/
°
F. However, the E5
j
J-F (Fahrenheit Model)
is factory-set to 14.4
°
F.
Integral Time :
i
When the character “
i
” is displayed on the PV display, the integral
time (I constant) can be changed using the Up and Down Keys. It
can be set in a range from 0 to 3,999 seconds in units of 1 second.
The value is factory-set to 233 seconds.
Derivative Time :
d
When the character “
d
” is displayed on the PV display, the deriva-
tive time (D constant) can be changed using the Up and Down Keys.
It can be set in a range from 0 to 3,999 seconds in units of 1 second.
The value is factory-set to 40 seconds.
Manual Reset Value Setting (%) :
ofr
The necessary output value in stable state will be set within a range
of 0.0% to 100.0%. The output value is factory-set to 50.0%. In P or
PD mode (i.e., when I is 0), the Temperature Controller will be bal-
anced with a deviation value between the set point and process val-
ue. This deviation value is called the offset. By changing the manual
reset value, the offset can be eliminated.
Engineering Level Parameters
The value set before shipping
appears. (see note 1)
Displayed if the E5
j
J with a com-
munications function is used.
(Data bit length setting)
(Parity check setting)
(Stop bit length setting)
Displayed if the E5
j
J is in 2-PID opera-
tion with fuzzy self-tuning.
(Stable range setting)
Displayed if the E5
j
J is in 2-PID opera-
tion.
(Alpha setting)
(Automatic return of display mode)
Displayed if the E5
j
J with an alarm
function is used (see note 2).
(Standby sequence
reset method setting)
(Input shift display selection)
Displayed if the E5
j
J with an alarm
function is used (see note 2).
(Alarm 1 hysteresis
setting)
Displayed if the E5
j
J with an alarm
function is used (see note 2).
(Alarm 2 hysteresis
setting)
(Set point lower limit setting)
(Set point upper limit setting)
Displayed if the E5
j
J with
event input 2 is used.
(Event input 2 function
selection)
Note:
1. The E5
j
J-
jjjj
-F values set before shipping
are different. Refer to the
E5
j
J Operation Manu
-
al (Z103).
2. The value will not be displayed if the alarm mode
switch is set to 0 or if the E5
j
J does not incorpo-
rate any alarm.
(
°
C/
°
F selection)
15.0