E5AJ/E5BJ/E5EJ
Output value
Press
a
o
(Output value display)
20
Press
a
cp
1.0
Press
a
hys
0
Press
a
spĆ0
Press
a
sPĆ1
Press
a
ct
0.0
Press
a
hb
8.0
Press
a
p
233
Press
a
i
40
Press
a
d
50.0
Press
a
ofr
ON/OFF
control
(Hysteresis
setting)
PID control
(Control period setting)
(Models with event input)
(Set point 0 setting SP0)
(Set point 1 setting SP1)
If control output is
current output.
(Heater current
value display)
(Heater burnout
alarm value setting)
If the control mode is set to
2-PID
(Proportional band setting)
(Integral time setting)
(Derivative time setting)
(Manual reset
value setting)
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
0
Current value
(see note)
When I = 0
1
2
3
4
O
N
1
2
3
4
O
N
1
2
3
4
O
N
(See note)
Without heater
burnout alarm
(See note)
Note:
Nothing is displayed in current output model.
Output Value Display:
o
Displayed range 0.0% to 100.0%
Control Period:
cp
The control period can be set with the Down and Up Keys within a
range of 1 to 99 s. The control period is factory-set to 20 s.
In the case of 2-PID, the relay output or voltage output repeats turn-
ing ON and OFF, the cycle of which is called a control period. The
duration that the output is ON is in proportion to the output value.
The shorter the control period is, the smoother the control operation
will be. If the control period is, however, too short, the life of the relay
will be shortened. Therefore the control period should be 20 s mini-
mum in the case of relay output.
ON
OFF
Control period:
10 seconds
ON
OFF
Control period:
20 seconds
Output Value: 50.0%
Hysteresis:
hys
The hysteresis value for the ON/OFF control can be set in a range
from 0.0
°
to 999.9
°
C/
°
F while “
hys
” is displayed on the PV display
using the Up and Down Keys. The value is factory-set to 1.0
°
C/
°
F.
However, the E5
j
J-F (Fahrenheit Model) is factory-set to 1.8
°
F.
Low temperature
set point
High temperature
Hysteresis
ON
OFF
Reverse operation
(heating control)
Hysteresis
ON
OFF
Normal operation
(cooling control)
Low temperature
set point
High temperature
Set Point 0 Setting (
°
C or
°
F):
spĆ0
Use the Down and Up Keys to set the set point 0. It is possible to set
the value regardless of whether the set value presently selected is
on SP0 or SP1.