background image

E3X-MDA

E3X-MDA

Adjustment Methods

1. Setting the Operation Mode

The operation mode is set in SET mode. Refer to page A-373 5. Set-
ting Functions in SET Mode
.

Set the Channel Selector to the desired channel before making any 
adjustments or settings. This is true for all adjustments and settings. 

2. Adjusting the Power (RUN Mode)

The current incident light level can be adjusted to near the power 
tuning target value (default: 2,000).

Confirm that the MODE key setting is PTUN (power tuning). The 
default setting is PTUN. Refer to page A-373 5. Setting Functions in 
SET Mode

* Setting Errors
An error has occurred if one of the following displays appears after 
the progress bar is displayed. 

Note: Press the DOWN key right after pressing the MODE key.

3.Setting Thresholds Manually 
(RUN Mode)

A threshold can be set manually. A threshold value can also be fine-
tuned using manual setting after teaching.

Even if the display method for display switching is changed, the 

threshold will appear on the sub-display when the key is pressed. 

4. Teaching the Threshold Value (SET Mode)

There are four methods that can be used for teaching, as described 

below. Use the method most suitable for the application.

An error has occurred if OVER, LO, or NEAR is displayed on the 

sub-display. Repeat the operation from the beginning. 

4-1. Setting the Threshold at Maximum Sensitivity

The threshold can be set at the maximum sensitivity. This method is 
ideal when using a Through-beam Fiber Unit to detect workpieces so 
that detection is not influenced to any great degree by dust and other 
environmental factors.

Display

Error

Action

Over Error

The incident light 

level is too low 

for the power tun-

ing target value.

The power will not be 

tuned. The power can 

be increased up to ap-

proximately 5 times 

the incident light val-

ue.

Bottom Error

The incident light 

level is too high 

for the power tun-

ing target value.

The power will be 

tuned to the minimum 

level. The power can 

be decreased down to 

approximately 1/25th 

the incident light val-

ue.

3 s

MODE

RUN

Release the key after
the progress bar
is displayed. 

The Power Tuning indicator
will light when the adjustment
has been completed. 

Light level

Threshold (default)

PTUN

Progress bar

Display changes after
specific time.

Power tuning
target value

Light level

Threshold

Set the Mode Se-
lector to RUN.

(Factory-set to RUN)

DOWN

MODE

3 s

The Power Tuning indicator
will go out when the default
setting has been restored.

"OFF" will flash twice.

To restore the default
power settings:

PTUN

OFF

Light level

Threshold

Press together (see note).

PTUN

OVER

Flashes twice

PTUN

BOTM

Flashes twice

UP

DOWN

Light level

Increases threshold.

Decreases threshold.

Threshold (default)

RUN

Set the Mode Se-
lector to RUN.

(Factory-set to RUN)

UP

DOWN

SET

The threshold value that 
was set will flash twice.

Light level

Threshold

FULL

Threshold

The previous display will 
return when the setting 
has been completed. 

Light level

Threshold

Set the Mode Selector  
to SET.

Either for 3 s

Summary of Contents for E3X-MDA11

Page 1: ...l from the Mobile Con sole The industry s first power tuning func tion in a digital amplifier Stable long term performance due to Omrons s APC function Two large easy to read displays The remarkable n...

Page 2: ...MDA Having problems gang mounting Fiber Sensor Amplifier Units in tight spaces 50 mm 100 mm Half the Space Incident level Operation indicator Channel 1 display Channel 2 display Incident level Operati...

Page 3: ...mm Remarkable space saving of approx 50 Power saving of approx 40 Savings per channel compared with existing products Detection and front back discrimination of parts Detection of bends in electronic...

Page 4: ...ir cuit is ON or OFF Time OMRON provides the industry s most stable long term detection by using new 4 element LEDs and an APC Auto Power Control circuit Time Without APC circuit Without APC circuit 3...

Page 5: ...output 2 channel models AND OR output E3X MDA11 E3X MDA41 Item Appearance Functions Model NPN output PNP output 2 channel models AND OR output E3X MDA6 E3X MDA8 Item Appearance Cable length No of con...

Page 6: ...from OFF delay ON delay or one shot timer 1 ms to 5 s 1 to 20 ms set in 1 ms increments 20 to 200 ms set in 10 ms increments 200 ms to 1 s set in 100 ms increments and 1 to 5 s set in 1 s increments A...

Page 7: ...nd Z directions Shock resistance destruction 500 m s2 for 3 times each in X Y and Z directions Enclosure rating IEC 60529 IP50 with Protective Cover attached Connection method Prewired cable Standard...

Page 8: ...tion indicator orange ON OFF Output transistor ON OFF Load relay Operate Release Between brown and black CH1 CH2 ON OFF ON OFF L ON D ON T T Incident light No incident light L ON D ON T T Incident lig...

Page 9: ...AND ON delay AND T T T One shot UP DOWN MODE Lock Button Locks the fiber Operation Keys Function setting operations Channel Selector Mode Selector Use to select SET or RUN mode ON when output is ON O...

Page 10: ...ximum sensitivity This method is ideal when using a Through beam Fiber Unit to detect workpieces so that detection is not influenced to any great degree by dust and other environmental factors Display...

Page 11: ...piece and the value between the two measured value can be set as the threshold UP DOWN RUN will be displayed With no workpiece The previous display will return when the setting has been completed The...

Page 12: ...rements of 100 Maximum power M Display orientation orientation To reverse the orientation of the display Up down reversed display Normal display 1 Light levels for channels 1 and 2 The incident light...

Page 13: ...N delay timer is selected the one shot timer is automati cally set i e the timer function cannot be selected Output for each channel Output when the output is ON for both channels 1 and 2 Output when...

Page 14: ...in To return to original value for incident light level Set the Mode Selector to RUN Factory setting 3 s Press together see note MODE MODE UP UP RUN OFF will flash twice and key operations will be ena...

Page 15: ...it Do not attempt to remove Connectors without separating them from other Amplifier Units first Joining and Removing Amplifier Units Joining Amplifier Units 1 Mount the Amplifier Units one at a time...

Page 16: ...to light from other sensors If this occurs decrease the sensitivity i e decrease the power or increase the threshold to perform stable detection EEPROM Writing Error If the data is not written to the...

Page 17: ...6 28 1 4 5 10 7 5 65 4 5 16 Two M3 E3X MDA11 E3X MDA41 Main display Sub display Vinyl insulated round cable Standard length 2 m Cable Specifications A 4 dia 2 conductor conductor cross sectional area...

Page 18: ...Diameters E3X CN11 3 conductors E3X CN21 4 conductors E3X CN22 2 conductors 4 0 mm dia E3X CN12 1 conductor 2 6 mm dia Connector Dia A 2 Hole for optical communications Mounting Holes First operation...

Page 19: ...ble conductor cross sectional area 0 2 mm2 insulation diameter 1 1 mm is used 136 50 52 8 22 Optical communications connection indicator Sensor operation indicator Main display Sub display RIGHT key E...

Page 20: ...erest of product improvement specifications are subject to change without notice Cat No E11E EN 01 OMRON EUROPE B V Wegalaan 67 69 NL 2132 JD Hoofddorf The Netherlands Phone 31 23 568 13 00 Fax 31 23...

Reviews: