E3X-MDA
E3X-MDA
• Fiber Connection
The E3X Amplifier Unit has a lock button for easy connection of the
Fiber Unit. Connect or disconnect the fibers using the following pro-
cedures:
1. Connection
Open the protective cover, insert the fibers according to the fiber
insertion marks on the side of the Amplifier Unit, and lower the lock
button.
Fibers with E39-F9 Attachment
Fibers That Cannot Be Free-Cut (with Sleeves)
2. Disconnecting Fibers
Remove the protective cover and raise the lock button to pull out the
fibers.
Note 1. To maintain the fiber properties, confirm that the lock is re-
leased before removing the fibers.
2. Be sure to lock or unlock the lock button within an ambient
temperature range between
−
10
°
C and 40
°
C.
Adjustments
• Mutual Interference Protection Function
There may be some instability in the digital display values due to light
from other sensors. If this occurs, decrease the sensitivity (i.e.,
decrease the power or increase the threshold) to perform stable
detection.
• EEPROM Writing Error
If the data is not written to the EEPROM correctly due to a power fail-
ure or static-electric noise, initialize the settings with the keys on the
Amplifier Unit. ERR/EEP will flash on the display when a writing error
has occurred.
• Optical Communications
Several Amplifier Units can be slid together and used in groups. Do
not, however, slide the Amplifier Units or attempt to remove any of
the Amplifier Units during operation.
Other Precautions
• Protective Cover
Always keep the protective cover in place when using the Amplifier
Unit.
• Mobile Console
Use the E3X-MC11-S Mobile Console for the E3X-DA-S-series and
the E3X-MDA series Amplifier Units. Other Mobile Consoles, such as
the E3X-MC11, cannot be used.
Lock button
Fiber
Fiber insertion
mark
Locked
Unlocked
Insertion position
Protective cover
9 mm
Fiber Unit
9 m m
1 3 m m
9 m m
1 3 m m
Locked
Unlocked
Protective cover