A - 31
Appendices
CJ-series EtherCAT Slave Units Operation Manual (W541)
A-6 F
INS Co
mm
and
s
A
A-6-
2 Det
ails o
n FINS C
ommands
Parameters
Error Log Data Format
Precautions
If the error log contains fewer records than the number specified in the number of records parame-
ter, all records stored in the error log at the time the command is executed will be returned and the
command executed will end normally.
End Code
Name
Description
Beginning record num-
ber (command)
Specify the first record to be read. The first record number can be specified in the range
between 0000 and 00F9 hex (0 to 249 decimal). The 0000 hex record is the oldest
record.
Number of records
(command)
The number of records to read is specified between 0001 and 0063 hex (1 to 99 deci-
mal).
Maximum number of
stored records
(response)
Indicates the maximum number of records that can be stored in the error log. The max-
imum number of error log records depends on the model of CPU Unit or CPU Bus Unit
being used. In an EtherCAT Slave Unit, the maximum number of stored records is fixed
at 00FA hex (250 decimal).
Number of stored
records (response)
The number of records stored at the time the command is executed is returned.
Number of read
records (response)
The number of actual records read is returned as a hexadecimal value.
Error log data
(response)
The specified number of error log records from the beginning record number is returned
sequentially. The total number of bytes in the error log is calculated as the number of
records x 10 bytes/record. Each error log record thus comprises 10 bytes. Refer to
Name
Description
Error code
Details of the error stored in the record. Refer to
5-15 for details.
Detailed information
Minute, Second, Day,
Hour, Year, Month
Indicates the time at which the error stored in the record occurred.
End code (hex)
Description
0000
Normal end
1001
Command too large
1002
Command too small
1103
Beginning record number is out of range
110C
The number of read records is 0000 hex
Error code Detailed
infor-
mation
1st byte
10th byte
Min. Sec. Day Hour Year Month
Summary of Contents for CJ1W- ECT21
Page 1: ...Cat No W541 E1 02 OPERATION MANUAL SYSMAC CJ Series CJ1W ECT21 EtherCAT Slave Unit ...
Page 8: ...CONTENTS 6 CJ series EtherCAT Slave Units Operation Manual W541 ...
Page 30: ...Revision History 28 CJ series EtherCAT Slave Units Operation Manual W541 ...
Page 32: ...Sections in this Manual 30 CJ series EtherCAT Slave Units Operation Manual W541 ...
Page 148: ...Appendices A 34 CJ series EtherCAT Slave Units Operation Manual W541 ...
Page 149: ...I 1 I CJ series EtherCAT Slave Units Operation Manual W541 Index ...
Page 152: ...I 4 CJ series EtherCAT Slave Units Operation Manual W541 Index ...
Page 153: ......