4 Exchanging Data with CPU
4-18
CJ-series High-speed Counter Units Operation Manual for NJ-series CPU Unit(W492)
*_DigiIn0FunCfg
WORD
R/W
Digital Input 0 Func-
tion/Counter Number
Bits 00 to 07: Sets the function for Digital Input 0.
16#00: No function (factory value)
16#01: Positive gate (Function 01)
16#02: Negative gate (Function 02)
16#03: Rising edge preset (Function 03)
16#04: Falling edge preset (Function 04)
16#05: Rising edge reset (Function 05)
16#06: Falling edge reset (Function 06)
16#15: Reset enabled (Function 15)
16#16: Reset disabled (Function 16)
(For details, refer to 3-4 Digital Input Functions.)
Bits 08 to 15: Sets the Counter connected to the
Digital Input 0.
16#00: No setting (factory value)
16#01: Counter 1
16#02: Counter 2
*_DigiIn1FunCfg
WORD
R/W
Digital Input 1 Func-
tion/Counter Number
Bits 00 to 07: Sets the function for Digital Input 1.
16#00: No function (factory value)
16#01: Positive gate (Function 01)
16#02: Negative gate (Function 02)
16#03: Rising edge preset (Function 03)
16#04: Falling edge preset (Function 04)
16#05: Rising edge reset (Function 05)
16#06: Falling edge reset (Function 06)
16#15: Reset enabled (Function 15)
16#16: Reset disabled (Function 16)
(For details, refer to 3-4 Digital Input Functions.)
Bits 08 to 15: Sets the Counter connected to the
Digital Input 1.
16#00: No setting (factory value)
16#01: Counter 1
16#02: Counter 2
*_PreOutPatCfg
DWORD R/W
Predefined Output Pat-
tern
When the output status control (Bits 12 to 15) in
*_OutStaCtlMdCfg is set in 16#02, the output pat-
tern set here (external internal output) is
applied to output.
Data range: 16#00000000 to 16#FFFFFFFF
Factory value: 16#00000000
Counter 1
*_Ch1_CtTypCfg
UINT
R/W
Counter Type
Sets the Counter type.
0: Circular Counter (factory value)
1: Linear Counter
Name of device variable
for CJ-series Unit
Type
R/W
Name
Function