2
.Installation and connection
11
(3) For EIA standard-compliant installation, use the included EIA rack fixing nuts (M5) and EIA/
JIS rack fixing screws (M5) to securely fasten the front and the back of the rack rails to the
server rack.
③
The screw hole positions are as follows.
• EIA rack : Topmost one for the front, topmost and bottommost ones for the rear
• JIS rack : One at the second from the bottom for both front and rear
(4) Use the 8 included bracket fixing screws (M4) (2 sets of 4 screws) to securely fasten the ear
brackets and unit guide rails to the left and right sides of the UPS.
④
(Installation is possible without removing the handles on the sides of BU5002RWL; do not
remove them.)
The support angles cannot be attached to special EIA/JIS racks.
(2) Adjust the length of support angles to suit the server rack, and then securely tighten the
screws that were half-tightened in step 1.
②
③
②
③
Rack fixing screws
Adjust the length to
suit the server rack
and tighten securely.
④
④
Summary of Contents for BU2002RWL
Page 60: ...10 48 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Page 61: ...10 Notes of Chinese 49 2 FA OA 2...
Page 62: ...BU2002RWL BU3002RWL BU5002RWL 10 50 AC 50 60Hz AC AC AC AC...
Page 63: ...10 Notes of Chinese 51 5cm 10cm UPS UPS AC AC AC200V 240V AC200 240V...
Page 65: ...10 Notes of Chinese 53 AC UPS AC UPS...
Page 66: ...BU2002RWL BU3002RWL BU5002RWL 10 54 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Page 67: ...10 Notes of Chinese 55 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...