![background image](http://html1.mh-extra.com/html/omron/bl100t/bl100t_instruction-manual_744583072.webp)
7 How to use optional cards
7-2 Contact signal I/O card
BL50T/BL75T/BL100T
72
7-2-2 Specifications
(Relay output type: SC08)
●
Signal output ( BU , BU, BL , BL, TR , TR, WB , WB)
Relay ratings
Applicable voltage: 30VDC or less
Maximum current: 2A (for resistive load)
1A (for inductive load)
●
Backup Power Supply Stop Signal input (
BS
, BS)
Input voltage: High (ON)
8 to 24VDC (for the 24V setting)
5 to 12VDC (for the 12V setting)
LOW (OFF) 0.7VDC or less
●
Remote ON/OFF
Voltage between terminals: 5VDC
Current when the circuit is closed
max.10mA
(Photo coupler type: SC07)
●
Signal output (BL, TR, BU, WB, BU )
Photo coupler ratings
Applicable voltage: 35VDC or less
Maximum current: 20mA
●
Backup Power Supply Stop Signal input (BS)
Input voltage: High (ON)
5 to 12VDC
Low (OFF)
0.7VDC or less
●
Remote ON/OFF
Voltage between terminals: 10VDC
Current when the circuit is closed
max.10mA
※
For details, see the manual that comes with the contact I/O card.