3 Names and functions of parts in the operation and display sections
3-1 Names and functions of parts in the operation and display sections
BL50T/BL75T/BL100T
32
■
Operation while the UPS is in use or AC input error
○:
Lit ON
●:
Lit OFF
UPS status
Icon
LED
Buzzer Output Charge Message at
top
Description
Solution
UPS event
●
●
●
None
OFF ON
Scheduled
startup
waiting
The USB is waiting for
scheduled startup.
-
BS signal
stopped
The BS signal is stopped. -
Remote
signal
stopped
The remote signal is
stopped.
-
Charge
waiting
The UPS is waiting for
charging.
The UPS cannot start
up due to
undercharge.
AC input
error-VH
AC input voltage error-
Voltage High
Use in the AC input
voltage range and
frequency described
in the specification.
Note: You can check
the input voltage by
selecting
"Measurement" menu
- "Input and Output".
AC input
error-VL
AC input voltage error-
Voltage Low
AC input
error-FH
AC input frequency error-
Frequency High
AC input
error-FL
AC input frequency error-
Frequency Low
■
Battery error
○:
Lit ON
●:
Lit OFF
UPS status
Icon
LED
Buzzer Output Charge Message at
top
Description
Solution
Battery
deterioration
(Flashing)
○
●
○
Intermitte
nt, at
intervals
of 2
seconds
ON
ON
Fault-E10
The self-diagnostic test
result indicates battery
deterioration.
Replace the battery.
Battery end
of life
○
○
(Note 4)
○
(Note 2)
Battery
end of life
The battery reached end of
life.
●
●
○
Battery
temperature
error (charge
stop)
(Flashing)
(Note 2)
●
●
Intermitte
nt, at
intervals
of 4
seconds
(Note 2)
ON
Fault-E12
(Note 3)
Charging is stopped
because the battery
temperature is high.
Check that the
ambient temperature
of the UPS is
between 0 and 40
degrees Celsius.
Fault-E14
Charging is stopped
because the battery
temperature is low.
No battery
connection
(Flashing)
○
●
○
Intermitte
nt, at
intervals
of 2
seconds
OFF ON
Fault-E11
The battery is not
connected.
Check the battery
cable connection.
●
●
○
Note 2: The power output is different depending on the operating condition.
Note 3: In power recovery immediately after backup operation ends, in rare cases, self-heating might occur in the
battery, activating the protection function, and the error (Fault-E12) might be displayed.
In that case, the commercial power is output as-is (charging stopped).
Then, the battery temperature drops, the error display is automatically canceled, and the charging
operation resumes.
Note 4: Different depending on the operating condition.