background image

2

Conductive Level Controller

 

61F-D21T-V1

Cat. No. N149-E1-03A

Ordering Information

List of Models

Specifications

Conductive Level Controller

Supply voltage

Model

24 VAC/DC

61F-D21T-V1 24 VAC/DC

100 to 240 VAC

61F-D21T-V1 100 to 240 VAC

Rated voltage

24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC, 50/60 Hz

Operating voltage range

85% to 110% of rated voltage

Voltage between electrodes

6 V p-p (approx. 20 Hz)

Power consumption

24 VDC: 2 W max.
24 VAC: 4 VA max. 
100 to 240 VAC: 5 VA max.

Operating resistance

10 k

 to 100 k

 (variable)

Reset resistance

250 k

 max.

Response time

Approx. 0.1 to 10 s (variable)

Cable length

100 m max. with completely insulated (600 V) cabtire cable with 3 conductors (0.75 mm

2

)

Control output

6 A at 250 VAC for resistive load at 20

°

C, 1 A at 250 VAC for inductive load cos

φ

 = 0.4 at 20

°

C

Indicators

Green LED: Power, Yellow LED: Control output

Ambient temperature

Operating: 

20 to 60

°

C, Storage: 

30 to 70

°

C (with no condensation or icing)

Ambient humidity

Operating: 25% to 85%, Storage: 25% to 85%

Elevation

2,000 m max.

Insulation resistance

100 M

 min. (at 500 VDC) between power supply section, electrode section, and contact section

Dielectric strength

2,000 VAC 50/60 Hz for 1 min between power source section, electrode section, and contact section

Vibration resistance

Vibration of 10 to 55 Hz and acceleration of 50 m/s

2

 for 5 min. 10 times each in X, Y, and Z directions

Shock resistance

100 m/s

2

 3 times each in 6 directions on 3 axes

Installation environment

Overvoltage Category II, Pollution Degree 2

Safety standards

EN61010-1

EMC

EN61326 Industrial applications

Summary of Contents for 61F-D21T-V1

Page 1: ...Delay timer to prevent relay contact chattering caused by waves Models with a wide AC power supply range 100 to 240 VAC and 24 VAC DC reduce the number of level controller models kept in stock CE mark...

Page 2: ...5 mm2 Control output 6 A at 250 VAC for resistive load at 20 C 1 A at 250 VAC for inductive load cos 0 4 at 20 C Indicators Green LED Power Yellow LED Control output Ambient temperature Operating 20 t...

Page 3: ...ndicator OFF and starts when the water level drops below E2 indicator ON 2 Drainage RY SW1 ON The pump starts when the water level reaches E1 indicator ON and stops when the water level drops below E2...

Page 4: ...hen relay is operating Item Usage Operating resistance knob Used to set the operating resistance to 10 to 100 k Operating time knob Use to set the operating time to 0 1 to 10 s Operating time knob Pow...

Page 5: ...ch the 61F D21T V1 to a DIN Rail DIN Rails PFP 100N 1 000 mm PFP 50N 500 mm Separator F03 14 Recommended Crimp Terminals 22 5 5 90 100 72 5 Two M4 screws or Two 4 5 dia holes Installation Procedure Mo...

Page 6: ...ations Places where there are extreme changes in temperature and humidity or icing or condensation may occur Places subject to static electricity or inductive noise Places subject to electrical fields...

Page 7: ...Cat No N149 E1 03A Conductive Level Controller 61F D21T V1 7...

Page 8: ...of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE...

Reviews: