48
2-8-6
Accel/Decel Time and Patterns
Item name
Constant to be set
Factory preset
Acceleration time 1
No. 9
10.0 s
Deceleration time 1
No. 10
10.0 s
Acceleration time 2
No. 11
10.0 s
Deceleration time 2
No. 12
10.0 s
Accel/Decel Time Select
No. 32 or No. 33
No. 32 = 1, No. 33 = 3
Each item can be set from 0.0 sec to 600.0 sec.
The set time indicates the interval required before the maximum
output frequency No. 2 is reached.
Time marked with
can be set for two-step switching using an
external contact.
The accel/decel time select command is input from multifunction
contact input terminals 4 and 5. Set the value of constant No. 32 to
6 to specify accel/decel time select operation for terminal 4, and
set the value of constant No. 33 to 6 to specify accel/decel time
select operation for terminal 5.
No. 2
No. 9
No. 12
No. 11
Output frequency
No. 10
Between control circuit terminals 4 or 5 and 6.
Open: No. 9 and 10 are selected.
Closed: No. 11 and 12 are selected.
Time
Output frequency
2-8-7
Output Frequency Control (Gain/Bias)
Item name
Constant to be set
Factory preset
Frequency command gain
No. 22
1.0
Frequency command bias
No. 23
0.00
Output frequency (gain/bias) can be set freely according to fre-
quency setting (0 to 10 V or 4 to 20 mA)
No. 22
0
100%
No. 23
10 V
(4 mA)
(20 mA)
Bias
(100% = 1.00)
Frequency setting
Gain
Description of Functions and Constants
Section 2-8