23
1-6-2 400-V-class Specifications
Inverter Model 3G3XV-
-EV2
A4002
A4004
A4007
A4015
A4022
A4037
Max. applicable motor output
1
Hp (kW)
0.25 (0.2)
0.5 (0.4)
1 (0.75)
2 (1.5)
3 (2.2)
5 (3.7)
Output char-
i i
Inverter capacity (kVA)
0.8
1.2
2.0
3.0
3.7
6.1
acteristics
Rated output current (A)
1
1.6
2.6
4
4.8
8
Max. output voltage
3-phase, 380 to 460 V (proportional to input voltage)
Max. output frequency
400 Hz (available with constant setting)
Power supply
Rated input voltage and fre-
quency
3-phase: 380 to 460 V, 50/60 Hz
Allowable voltage fluctuation
10%
Allowable frequency fluctua-
tion
5%
Control char-
i i
Control method
Sine wave PWM
acteristics
Frequency control range
0.1 to 400 Hz
Frequency accuracy
Digital command:
0.01% (14
°
to 104
°
F, –10
°
to 40
°
C)
Analog command: 0.1% (77
°
50
°
F, 25
°
10
°
C
Frequency resolution
Digital Operator reference: 0.1 Hz.
Analog reference:
0.06 Hz/60 Hz
Output frequency resolution
0.1 Hz
Overload capacity
150% rated output current for one minute
Frequency setting signal
0 to 10 VDC (20 k
Ω
), 4 to 20 mA (250
Ω
)
Accel/decel time
0.1 to 600 sec (accel/decel time setting independently)
Braking torque
Approx. 20% (up to 150% possible with optional braking
resistor externally mounted, braking resistor built-in)
V/f characteristic
Possible to set any program of V/f pattern
Stall prevention level
Possible to set operating current
Protective
f
i
Instantaneous overcurrent
Motor coasts to a stop at approx. 200% rated current.
functions
Overload
Motor coasts to a stop for 1 minute at 150% rated output
current
Ground fault
Provided by electronic circuit.
Motor overload protection
Electronic thermal overload relay
Overvoltage
Motor coasts to stop if main circuit DC voltage exceeds
820 V.
Undervoltage
Stops if the main circuit DC voltage is approx. 420 V or less.
Momentary power loss
Immediately stops if 15 ms or more momentary power loss.
Resumes operating after a power loss period of approxi-
mately 2 s if the input is 1.5 kW or more and approximately
1 s if the input is 0.75 kW or less in a certain mode.
Cooling fin overheat
Protected by thermoswitch (only for forced cooling method)
Power charge indication
CHARGE indicator stays ON until main circuit DC voltage
drops below 50 V.
Specifications
Section 1-6