13

MV MX 

Model 

Function 

No. 

Set 

value

No. 

Set 

value 

Remarks 

Multi function analog current 

input filter time constant 

n073 0.10 

―――

 

―――

 

 

Pulse train frequency 

reference gain 

n074 100 

―――

 

―――

 

 

Pulse train frequency 

reference bias 

n075 0 

―――

 

―――

 

 

Pulse train frequency 

reference input filter time 

constant  

n076 0.10 

―――

 

―――

 

 

Multi function analog input 

terminal function selection 

n077 0 

―――

 

―――

 

 

Multi function analog input 

terminal selection 

n078 0 

―――

 

―――

 

 

Multi function analog input 

frequency bias value 

n079 10 

―――

 

―――

 

 

Carrier frequency 

n080 

Varies 

with  

capacity

b083 5.0 

 

Operation after momentary 

power interruption and 

return selection 

n081 0 

Number of fault retries 

n082

 

b001 to 

b005 

―――

 

Set b001=1or 2.     

Execute error retry to over voltage   

  and over current at b005=0.   

The numbers of retry is fixed at 3.

 

Jump frequency 1 

n083 

0.00 

A063 

0.0 

Jump frequency 2 

n084 

0.00 

A065 

0.0 

Jump frequency 3 

n085 

0.00 

A067 

0.0 

Jump width 

n086 

0.00 

A064 
A066 
A068 

0.5 

MV:

 

set output frequency for jump as

 

n083 

to 085 and set jump width to n086. 
 
MX: set frequency command for jump as 
A063

065

067. Set jump frequency width 

on A064

066

068. 

Accumulated operating 

 time select 

n087 0 

―――

 

―――

 

Accumulated operating time 

n088 

d016 
d017 

―――

 

MV

  select monitoring time on n087 and 

n088 displays cumulative operation time. 

MX:d016:accumulated operation on RUN 

d017:Power ON time 

DC injection breaking   

current 

n089 50  A054  50 

 

DC injection 

breaking-to-stop time 

n090 0.5  A055  0.5 

 

DC injection breaking time 

at startup 

n091 0.0 

―――

 

―――

 

 

Stall prevention during 

deceleration select 

n092 0  b130  00 

MX:

 

set level on b131. 

Stall prevention operation 

level during deceleration 

n093 170  b140  00 

MX:ON/OFF setting only 

Detection level is 160% fixed 

Summary of Contents for 3G3MX-A2001

Page 1: ...1 3G3MV 3G3MX Migration guide...

Page 2: ...RCUIT TERMINAL 4 CONTROL CIRCUIT TERMINAL 5 THE DIFFERENCES ON TERMINAL SCREW AND WIRE SIZE BETWEEN MV AND MX 6 4 STANDARD BRAKING TORQUE AND MINIMUM CONNECTABLE RESISTANCE VALUE 8 5 PARAMETER TABLE 1...

Page 3: ...r of multi function analog input usable on the MX is one Change to MX is not possible if two analog inputs are used on the MV 4 The functions below are not available on the MX Frequency reference loss...

Page 4: ...dimensions of the MX drive are larger than the MV series Please note that the size value is larger than the MV depending on capacity The mounting screw position on 3G3MV AE002 AE004 A2002 to 2007 diff...

Page 5: ...MV MX Remarks R L1 R L1 S L2 S L2 T L3 T L3 AC power input terminal U T1 U T1 V T2 V T2 W T3 W T3 Motor output terminal B1 P 2 B2 RB Braking resistor connection terminal 1 1 DC reactor connection term...

Page 6: ...ent on the MV and MX drives The default value will display the multi function setting allocated on both MV and MX On the default setting the control terminals of S3 and S4 on MV have switched to the o...

Page 7: ...nd wire size differences between MV and MX Main circuit terminal size and electrical wire size Recommended wiring breaker and electromagnetic contactor will be same Control circuit terminal size and e...

Page 8: ...s 0 5mm 2 The length to signal line armor is 5 to 6mm and connect it as an electrical wire If stranded wire keep it from coming apart The max armor outer dimensions of signal line except alarm signal...

Page 9: ...in the shortest time From 60Hz on a single unit motor MX the average deceleration torque when deceleration in the shortest time From 50Hz on a single unit motor Braking resistor is not installed on in...

Page 10: ...10 bold Depending on cases please consider using a larger capacity drive Minimum connectable resistance value on each capacity Following is the braking options used on MX...

Page 11: ...selection at operator interruption n010 0 Maximum frequency n01 1 60 0 A004 60 0 Maximum voltage n012 200 0 A082 200 Maximum voltage frequency n013 60 0 A003 60 0 Middle output frequency n014 1 5 A04...

Page 12: ...pper frequency reference limit n033 100 A061 0 0 The default value of MX 0 0 shows limit function invalid Lower frequency reference limit n034 0 A062 0 0 Frequency reference select reference unit sele...

Page 13: ...081 C082 100 0 100 0 C081 Gain adjustment at voltage input C082 Gain adjustment at current input Frequency reference bias n061 0 A01 1 A101 0 0 0 0 A011 Bias adjustment at voltage input A101 Bias adju...

Page 14: ...umbers of retry is fixed at 3 Jump frequency 1 n083 0 00 A063 0 0 Jump frequency 2 n084 0 00 A065 0 0 Jump frequency 3 n085 0 00 A067 0 0 Jump width n086 0 00 A064 A066 A068 0 5 MV set output frequenc...

Page 15: ...ng at same frequency on trip retry function Torque compensation gain n103 1 0 A046 1 0 Torque compensation primary delay time constant n104 0 3 Torque compensation excitation loss n105 Varies with cap...

Page 16: ...A071 00 Detection value adjustment gain n129 1 00 A075 1 00 MV Adjust input level of target value MX Set percentage of feedback value and display it on monitor d004 Proportional gain P n130 1 0 A072...

Page 17: ...t used n147 n148 Pulse train input scale n149 2500 Multi function analog output pulse train frequency selection n150 0 RS 422 485 communication time over detection selection n151 0 C076 C077 02 0 00 C...

Page 18: ...sed n165 Input open phase detection level n166 0 Input open phase detection time n167 0 Output open phase detection level n168 0 Output open phase detection time n169 0 0 Enter command operation selec...

Page 19: ...0 10 0 AE022 3 8 11 0 5 0 No decrease of rating Single phase 200V AB037 6 7 17 5 7 5 16 5 A2001 0 3 0 8 A2002 0 6 1 6 A2002 0 6 1 6 A2004 1 1 3 0 A2004 1 0 3 0 A2007 1 9 5 0 10 No decrease of rating A...

Page 20: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 21: ...mron247 com Canada www omron ca Brazil www omron com br Latin America www espanol omron com MIG_MAN_3G3MVTO3G3MX 2008 OMRON ELECTRONICS LLC UNITED STATES To locate a Regional Sales Office local Distri...

Reviews: