5 Parameter table
MV MX
Model
Function
No.
Set
value
No.
Set
value
Remarks
Parameter write-prohibit
selection/ initial constant
n001 1
b031
b084
01
00
b031:Parameter protection function
b084: Parameter initialization select
Control mode selection
n002
0
A044
02
The default value of MX series is vector
control.
RUN command selection
n003
0
A002
02
Frequency reference
selection
n004 0 A001 00
Stopping method selection n005
0
b091
00
Reverse rotation-prohibit
selection
n006 0
―――
―――
STOP key enabled/
disabled selection
n007 0 b087 00
Frequency reference
selection on local mode
n008 0
―――
―――
Operator frequency
setting method selection
n009 0
―――
―――
Operation selection at
operator interruption
n010 0
―――
―――
Maximum frequency
n011 60.0 A004 60.0
Maximum voltage
n012 200.0
A082
200
Maximum voltage frequency n013 60.0 A003 60.0
Middle output frequency
n014 1.5 A043 3.0
Middle output frequency
voltage
n015 12.0 A042 5.0
Minimum output frequency n016 1.5 b082 0.5
Minimum output frequency
voltage
n017 12.0
―――
―――
V/f pattern setting
∗
Set
middle
output frequency and vol
ume
with % to the max value.
Acceleration/Deceleration
setting unit
n018 0
―――
―――
Acceleration time1
n019
10.0
F002
10.0
Deceleration time 1
n020 10.0 F003 10.0
Acceleration time 2
n021
10.0
A092
15.00
Deceleration time 2
n022
10.0
A093
15.00
S-shape
acceleration/deceleration
characteristics selection
n023 0
A097
A098
00
00
A097:Acceleration characteristics
A098:Deceleration characteristics
[b082]
[n016]
[A043]
[n014]
[A003]
[n013]
[A004]
[n011]
[MX]
[MV]
(Hz)
[A082][n012]
[A042][n015]
[---][n017]
[MX] [MV]
(V)
10