background image

Check output for short circuit or ground fault.

The Load is too large, reduce it or use larger Inverter.

Check motor FLA rating compared to Inverter and V/F setting.

Load inertia is too large and the motor is regenerating.

Increase deceleration time (n020 or n022).

Connect an external braking resistor and set n092 to 1.

Check braking resistor and wiring.

Check mains power supply voltage and connections.

Check correct supply for Inverter being used.

Monitor for mains dips or interruptions.

Refer to manual for installation guidelines and recommendations.

Check cooling fan (if fitted).

Check V/F characteristic or reduce Carrier frequency.

Check and reduce the load.

Check V/F characteristic (Vmax and Fmax).

Increase the running speed of the motor.

Increase acceleration/deceleration times.

Check your control terminal wiring.

A multi-functional digital input has been set to 3 or 4.

Run signal must be removed before this can be reset.

Inverter must be stopped when Local/Remote switching

attempted.

Inverter must be stopped when Comms/Remote switching

attempted.

Check your control terminal wiring.

A multi-function digital input has been set to 12 or 13.

Forward and reverse run signal have been applied 

simultaneously.

Overcurrent

Output current is higher than

250% of Inverter rated current.

Overvoltage

DC bus voltage has exceeded

detection level.

Main circuit undervoltage

DC bus voltage is below 

detection level.

Unit overheated

Temperature inside the inverter

has exceeded 110°C.

Motor overload

The Inverter is protecting the motor

from overload based on an internal

I≈T calculation using n036 setting.

External fault

An external fault has been input.

Sequence error

Sequence input when Inverter

running.

External baseblock

An external baseblock command

has been input.

Sequence error has occurred

OC

OV

uV1

OH

OL1

EF*

SER

(flashing)

bb

(flashing)

EF

(flashing)

Fault Display

Fault name and meaning

Possible cause and remedy

Protective and Diagnostic Functions

Note:

Refer to Section 7-2 for full fault code listings.

Improper  procedures  can  result  in  personal  injury  or
equipment damage. Use the Quick Start Guide only if you
are  familiar  with  standard  safety  precautions  common  to
variable  speed  drives.  See  Operation  Manual  I528  for 
further details.

Summary of Contents for 3G3JV Series

Page 1: ... eu omron com 1 Apsley Way Staples Corner London NW2 7HF Fax number 020 8233 1468 Factory automation technical support 24hr technical helpsheet datasheet faxback service 020 8450 4646 General telephone enquiries and technical support UK website Direct e mail address for sales enquiries ...

Page 2: ...ply 20mA at 12V Frequency reference input Frequency reference common Multi function contact output NC L1í L2í L3í External frequency adjuster 2 kΩ 1 4 W min Multi function input 2 S3 Multi function input 3 S4 Multi function input 4 S5 Analogue monitor output M 3G3JV PFI Standard Connections Note 1 Connect single phase 200 V AC to terminals R L1 and S L2 of the 3G3JV AB Note 2 The braking resistor ...

Page 3: ... Set by parameter n40 during running Common for MA amd MB use Set by parameter n44 Output frequency Common for AM use Photocoupler 8 mA at 24VDC Note NPN is the default setting for these terminals No external power supply is required Refer to connections shown below 20mA at 12VDC 0 to 10VDC 20Kohms 4 to 20mA 0 to 20mA Relay output 1A max at 30VDC and 250 VAC 12mA max at 0 to 10VDC S1 S2 S3 S4 S5 S...

Page 4: ...I3005E PFI3010E PFI3010E PFI3010E PFI3020E PFI3020E Installation Dimensions Rated Voltage Model 3G3JV Supply Recommendations Noise Filter Specifications Y W X d H L D 8 5 H1 H W1 W 5 6 Two 5 dia holes 5 H 128 128 128 128 128 128 128 128 128 128 128 128 H1 118 118 118 118 118 118 118 118 118 118 118 118 W 68 68 68 108 108 108 108 108 108 108 140 140 W1 56 56 56 96 96 96 96 96 96 96 128 128 D 70 70 ...

Page 5: ...ugh to n79 can be set or moni tored while this indicator is lit Note While the Inverter is in operation the parameters can be only monitored and only some parameters can be changed Any RUN command input is ignored while this indicator is lit Switches the setting and monitor item indicators in sequence Parameter being set will be cancelled if this key is pressed before entering the setting Increase...

Page 6: ...r Output 0 Output Frequency 1 Output Current Carrier Frequency Selection DC Injection Braking Current DC Injection Braking at Stop Time DC Injection Braking at Start Time Stall pevention during deceleration 0 Stall Prevention Enabled 1 Braking Resistor Enabled n01 n02 n03 n09 n10 n11 n16 n17 n21 n22 n28 n32 n36 n37 n38 n39 n40 n44 n46 n52 n53 n54 n55 0 to 9 0 1 0 to 4 20 to 400 1 to 255V 0 2 to 40...

Page 7: ...peed reference 1 7 Multi step speed reference 2 8 Multi step speed reference 3 10 Inching command 12 External base block NO 13 External base block NC 17 Local Remote selection Multi function Outputs Value Function 0 Fault output 1 During RUN 2 Frequency agree 6 Overtorque being monitored NO 12 RUN mode 13 Inverter ready 15 Undervoltage in progress Analogue Output Functions Value Function 0 Output ...

Page 8: ...n Comms Remote switching attempted Check your control terminal wiring A multi function digital input has been set to 12 or 13 Forward and reverse run signal have been applied simultaneously Overcurrent Output current is higher than 250 of Inverter rated current Overvoltage DC bus voltage has exceeded detection level Main circuit undervoltage DC bus voltage is below detection level Unit overheated ...

Reviews: