background image

L

169

169

169

169

169

169

169

169

169

169

174

174 

W

71

71

71

111

111 

111 

111 

111 

111 

111 

144

144 

H

45

45

45

50

50 

50 

50 

50

50 

50 

50 

50 

X

156

156

156

156

156 

156 

156 

156 

156 

156 

161 

161 

Y

51

51

51

91

91 

91 

91 

91 

91 

91 

120

120 

d

5

5

5

5

5

M5 

M5

M5

M5

M5

M5

M5 

Model 
3G3JV

AB001

AB002

AB004

AB007

AB015

A4002

A4004

A4007

A4015

A4022

A4030

A4040

Filter 
3G3JV

PFI1010E

PFI1010E

PFI1010E

PFI1020E

PFI1020E

PFI3005E

PFI3005E

PFI3010E

PFI3010E

PFI3010E

PFI3020E

PFI3020E

Installation

Dimensions

Rated

Voltage

Model

3G3JV-

Supply Recommendations

Noise Filter Specifications

Y

W

X

d

H

L

D

8.5

H1

H

W1

W

5
6

Two, 5 dia. holes

5

H

128

128

128

128

128

128

128

128

128

128

128

128

H1

118

118

118

118

118

118

118

118

118

118

118

118

W

68

68

68

108

108

108

108

108

108

108

140

140

W1

56

56

56

96

96

96

96

96

96

96

128

128

D

70

70

112

129

154

81

99

129

154

154

161

161

AB001

AB002

AB004

AB007

AB015

A4002 

A4004 

A4007 

A4015 

A4022 

A4030 

A4040 

Single Phase
200 VAC

MCCB (A)

5

5

10

20

20

5

5

5

10

10

20

20

Wire (mm2)

2

2

2

3.5

5.5

2

2

2

3.5

3.5

5.5

5.5

Summary of Contents for 3G3JV Series

Page 1: ... eu omron com 1 Apsley Way Staples Corner London NW2 7HF Fax number 020 8233 1468 Factory automation technical support 24hr technical helpsheet datasheet faxback service 020 8450 4646 General telephone enquiries and technical support UK website Direct e mail address for sales enquiries ...

Page 2: ...ply 20mA at 12V Frequency reference input Frequency reference common Multi function contact output NC L1í L2í L3í External frequency adjuster 2 kΩ 1 4 W min Multi function input 2 S3 Multi function input 3 S4 Multi function input 4 S5 Analogue monitor output M 3G3JV PFI Standard Connections Note 1 Connect single phase 200 V AC to terminals R L1 and S L2 of the 3G3JV AB Note 2 The braking resistor ...

Page 3: ... Set by parameter n40 during running Common for MA amd MB use Set by parameter n44 Output frequency Common for AM use Photocoupler 8 mA at 24VDC Note NPN is the default setting for these terminals No external power supply is required Refer to connections shown below 20mA at 12VDC 0 to 10VDC 20Kohms 4 to 20mA 0 to 20mA Relay output 1A max at 30VDC and 250 VAC 12mA max at 0 to 10VDC S1 S2 S3 S4 S5 S...

Page 4: ...I3005E PFI3010E PFI3010E PFI3010E PFI3020E PFI3020E Installation Dimensions Rated Voltage Model 3G3JV Supply Recommendations Noise Filter Specifications Y W X d H L D 8 5 H1 H W1 W 5 6 Two 5 dia holes 5 H 128 128 128 128 128 128 128 128 128 128 128 128 H1 118 118 118 118 118 118 118 118 118 118 118 118 W 68 68 68 108 108 108 108 108 108 108 140 140 W1 56 56 56 96 96 96 96 96 96 96 128 128 D 70 70 ...

Page 5: ...ugh to n79 can be set or moni tored while this indicator is lit Note While the Inverter is in operation the parameters can be only monitored and only some parameters can be changed Any RUN command input is ignored while this indicator is lit Switches the setting and monitor item indicators in sequence Parameter being set will be cancelled if this key is pressed before entering the setting Increase...

Page 6: ...r Output 0 Output Frequency 1 Output Current Carrier Frequency Selection DC Injection Braking Current DC Injection Braking at Stop Time DC Injection Braking at Start Time Stall pevention during deceleration 0 Stall Prevention Enabled 1 Braking Resistor Enabled n01 n02 n03 n09 n10 n11 n16 n17 n21 n22 n28 n32 n36 n37 n38 n39 n40 n44 n46 n52 n53 n54 n55 0 to 9 0 1 0 to 4 20 to 400 1 to 255V 0 2 to 40...

Page 7: ...peed reference 1 7 Multi step speed reference 2 8 Multi step speed reference 3 10 Inching command 12 External base block NO 13 External base block NC 17 Local Remote selection Multi function Outputs Value Function 0 Fault output 1 During RUN 2 Frequency agree 6 Overtorque being monitored NO 12 RUN mode 13 Inverter ready 15 Undervoltage in progress Analogue Output Functions Value Function 0 Output ...

Page 8: ...n Comms Remote switching attempted Check your control terminal wiring A multi function digital input has been set to 12 or 13 Forward and reverse run signal have been applied simultaneously Overcurrent Output current is higher than 250 of Inverter rated current Overvoltage DC bus voltage has exceeded detection level Main circuit undervoltage DC bus voltage is below detection level Unit overheated ...

Reviews: