background image

NPN

PNP

SW7

SW7

OFF

SW8

SW8

V

I

Control circuit

terminal block

Control circuit

terminal block

Forward/Stop

Multi-function Input 1

Multi-function input 2

Multi-function input 3

Multi-function input 4

Sequence Input Common 

Frequency reference Power Supply

Frequency Reference Input

Frequency Reference Common

Multi-function output: NO

Multi-function output: NC

Multi-function output Common

Analogue Monitor output

Analogue Monitor output Common

Forward at ON/Stops at OFF

Set by parameter n36 

(Reverse/Stop) 

Set by parameter n37 

(External Fault: NO)

Set by parameter n38 (Fault Reset)

Set by parameter n39 

(Multi-step reference 1)

Common for S1 through S5

DC power supply for frequency 

reference use

Input terminal for frequency 

reference use

Common for frequency 

reference use

Set by parameter n40 

(during running)

Common for MA amd MB use

Set by parameter n44 

(Output frequency)

Common for AM use

Photocoupler

8 mA at 24VDC

Note:

NPN is the

default setting for

these terminals. 

No external power

supply is required.

Refer to connections

shown below.

20mA at 12VDC

0 to 10VDC

(20Kohms)

4 to 20mA

0 to 20mA

Relay output

1A max. at 30VDC

and 250 VAC

12mA max. at 0 to

10VDC

S1

S2

S3

S4

S5

SC

FS

FR

FC

MA

MB

MC

AM

AC

Input

Output

Control Circuit Terminals

Selecting Input Method

Symbol

Name

Function

Signal Level

Note:

Functions in parentheses are default settings.

Switches SW7 and SW8, both of which are
located above the control circuit terminals,
are used for input method selection.

Remove the front cover and optional cover
to use these switches.

Selecting Sequence Input Method

By using SW7, NPN or PNP input can be selected as shown below.

360

24V

SW7

GND

GND

SC

S1 to 5

3.3k

0.1

µ

(Default setting)

GND

SC

360

SW7

24V

S1 to 5

24 V DC

3.3k

GND

(±10%)

0.1

µ

NPN

PNP

Summary of Contents for 3G3JV Series

Page 1: ... eu omron com 1 Apsley Way Staples Corner London NW2 7HF Fax number 020 8233 1468 Factory automation technical support 24hr technical helpsheet datasheet faxback service 020 8450 4646 General telephone enquiries and technical support UK website Direct e mail address for sales enquiries ...

Page 2: ...ply 20mA at 12V Frequency reference input Frequency reference common Multi function contact output NC L1í L2í L3í External frequency adjuster 2 kΩ 1 4 W min Multi function input 2 S3 Multi function input 3 S4 Multi function input 4 S5 Analogue monitor output M 3G3JV PFI Standard Connections Note 1 Connect single phase 200 V AC to terminals R L1 and S L2 of the 3G3JV AB Note 2 The braking resistor ...

Page 3: ... Set by parameter n40 during running Common for MA amd MB use Set by parameter n44 Output frequency Common for AM use Photocoupler 8 mA at 24VDC Note NPN is the default setting for these terminals No external power supply is required Refer to connections shown below 20mA at 12VDC 0 to 10VDC 20Kohms 4 to 20mA 0 to 20mA Relay output 1A max at 30VDC and 250 VAC 12mA max at 0 to 10VDC S1 S2 S3 S4 S5 S...

Page 4: ...I3005E PFI3010E PFI3010E PFI3010E PFI3020E PFI3020E Installation Dimensions Rated Voltage Model 3G3JV Supply Recommendations Noise Filter Specifications Y W X d H L D 8 5 H1 H W1 W 5 6 Two 5 dia holes 5 H 128 128 128 128 128 128 128 128 128 128 128 128 H1 118 118 118 118 118 118 118 118 118 118 118 118 W 68 68 68 108 108 108 108 108 108 108 140 140 W1 56 56 56 96 96 96 96 96 96 96 128 128 D 70 70 ...

Page 5: ...ugh to n79 can be set or moni tored while this indicator is lit Note While the Inverter is in operation the parameters can be only monitored and only some parameters can be changed Any RUN command input is ignored while this indicator is lit Switches the setting and monitor item indicators in sequence Parameter being set will be cancelled if this key is pressed before entering the setting Increase...

Page 6: ...r Output 0 Output Frequency 1 Output Current Carrier Frequency Selection DC Injection Braking Current DC Injection Braking at Stop Time DC Injection Braking at Start Time Stall pevention during deceleration 0 Stall Prevention Enabled 1 Braking Resistor Enabled n01 n02 n03 n09 n10 n11 n16 n17 n21 n22 n28 n32 n36 n37 n38 n39 n40 n44 n46 n52 n53 n54 n55 0 to 9 0 1 0 to 4 20 to 400 1 to 255V 0 2 to 40...

Page 7: ...peed reference 1 7 Multi step speed reference 2 8 Multi step speed reference 3 10 Inching command 12 External base block NO 13 External base block NC 17 Local Remote selection Multi function Outputs Value Function 0 Fault output 1 During RUN 2 Frequency agree 6 Overtorque being monitored NO 12 RUN mode 13 Inverter ready 15 Undervoltage in progress Analogue Output Functions Value Function 0 Output ...

Page 8: ...n Comms Remote switching attempted Check your control terminal wiring A multi function digital input has been set to 12 or 13 Forward and reverse run signal have been applied simultaneously Overcurrent Output current is higher than 250 of Inverter rated current Overvoltage DC bus voltage has exceeded detection level Main circuit undervoltage DC bus voltage is below detection level Unit overheated ...

Reviews: