3-10
D
Output Terminals (On Right-hand Side)
Terminal
symbol
Name and description
Interface
PA
Multi-function photocoupler output (see note)
PC
Multi-function photocoupler output (common)
50 mA at 48 VDC max.
Note
Constant No. 10 (n10) is used to set this function. This constant is factory-set to “fault.”
The standard model does not have multi-function photocoupler output.
D
Analog Output Terminals (On Right-hand Side)
Terminal
symbol
Name and description
Interface
AM
Multi-function analog output (see note)
AC
Multi-function analog output (common)
2 mA at
0 to +10 VDC max.
Note
Constant No. 44 (n44) is used to set this function and constant No. 45 (n45) is used to set the
multiplying factor, which are factory-set to “output frequency” and “3V at maximum frequency”
respectively.
The standard model does not have analog output.
H
Standard Connection Diagram
D
Main Circuit Terminal Connections
Three-phase,
200 VAC
Single-phase,
200 VAC
Three-phase,
400 VAC
Circuit
breaker Noise Filter
Braking Unit (Optional)
Clamp core
Note 1.
Three-phase 200 VAC (400 VAC) can be input to L1, L2, and L3.
Note 2.
For the 400-VAC-class Inverter, be sure to ground the supply neutral.
Design
Chapter 3
Summary of Contents for 3G3EV-A2001-CUE
Page 8: ......
Page 11: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 14: ...Chapter 2 Overview 2 1 Features 2 2 Nomenclature 2...
Page 19: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 41: ...Chapter 4 Specifications 4 1 Specifications of Main Unit 4 2 Specifications of Noise Filter 4...
Page 48: ...4 8 D 3G3EV PNF2003A YN PNF2010A YN Two 5 0 dia max 1 Specifications Chapter 4...
Page 49: ...4 9 D 3G3EV PNF2020A YN 5 0 dia 5 93 1 118 1 128 2 74 2 56 1 74 max Specifications Chapter 4...