3-4
D
Three-phase 400-VAC Input Model
3G3EV model
Output
W
H
D
W1
H1
Weight (kg)
A4002(M)-CUE
0.2 kW
108
128
92
96
118
Approx. 1.0
A4004(M)-CUE
0.4 kW
110
Approx. 1.0
A4007(M)-CUE
0.75 kW
140
Approx. 1.5
A4015(M)-CUE
1.5 kW
130
170
118
Approx. 2.0
3-1-2 Installation Conditions
H
Installation Site
•
Install the Inverter under the following conditions:
Ambient temperature for operation: –10
°
C to 50
°
C
Humidity: 90% RH or less (non-condensing)
•
Install the Inverter in a clean location free from oil mist and dust. Alternatively, install it in a totally en-
closed panel that is completely shielded from suspended dust.
•
When installing or operating the Inverter, always take special care so that metal powder, oil, water, or
other foreign matter do not get in the Inverter.
•
Do not install the Inverter on inflammables such as wood.
H
Direction of Installation
•
Install the Inverter on a vertical surface so that the characters on the nameplate are oriented upward.
H
Installation Space
•
When installing the Inverter, always provide the following installation space to allow normal heat dis-
sipation from the Inverter:
W= 30 mm min.
100 mm min.
100 mm min.
Air
Side
Air
Inverter
Inverter
Inverter
Design
Chapter 3
Summary of Contents for 3G3EV-A2001-CUE
Page 8: ......
Page 11: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 14: ...Chapter 2 Overview 2 1 Features 2 2 Nomenclature 2...
Page 19: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 41: ...Chapter 4 Specifications 4 1 Specifications of Main Unit 4 2 Specifications of Noise Filter 4...
Page 48: ...4 8 D 3G3EV PNF2003A YN PNF2010A YN Two 5 0 dia max 1 Specifications Chapter 4...
Page 49: ...4 9 D 3G3EV PNF2020A YN 5 0 dia 5 93 1 118 1 128 2 74 2 56 1 74 max Specifications Chapter 4...