Solderless Terminals for Control Circuit Terminals
The use of solderless terminals for the control circuit terminals is recommended because solderless
terminals are easy to connect securely.
d1 dia.
d2 dia.
Wire thickness
Model
d1
d2
Manufacturer
Terminal
0.5 mm
2
A1 0.5-8WH
1.00
2.60
Phoenix Contact
SF, SR, S1 to
S3, SC, FS, FR,
FC
0.7 mm
2
A1 0.75-8GY
1.20
2.80
MA, MB, MC
1 mm
2
A1 1-8RD
1.40
3.00
,
,
D
Wiring Method
•
Wire each terminal as follows:
a) Loosen the terminal screw with a thin-slotted screwdriver.
b) Insert the wire from underneath the terminal block.
c) Tighten the terminal screw firmly.
•
Always separate the control signal line from the main circuit cables and other power cables.
•
Insulate the shielded sections with insulation tape, etc., from other signal lines or equipment and
ground on the Inverter side.
Thin-slotted screwdriver
Length of stripped
portion: Approx. 5.5 mm
Wire
Control circuit
terminal block
Do not solder this portion.
(Otherwise, faulty contact may result.)
Design
Chapter 3
Summary of Contents for 3G3EV-A2001-CUE
Page 8: ......
Page 11: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 14: ...Chapter 2 Overview 2 1 Features 2 2 Nomenclature 2...
Page 19: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 41: ...Chapter 4 Specifications 4 1 Specifications of Main Unit 4 2 Specifications of Noise Filter 4...
Page 48: ...4 8 D 3G3EV PNF2003A YN PNF2010A YN Two 5 0 dia max 1 Specifications Chapter 4...
Page 49: ...4 9 D 3G3EV PNF2020A YN 5 0 dia 5 93 1 118 1 128 2 74 2 56 1 74 max Specifications Chapter 4...