PRELIMINARY
TRIPARK 25
10
8.2.
Electric supply system
The electric supply system must include:
a general switch with padlockable circuit breaker;
fuses or thermal magnet protection suited to the machine’s
characteristics;
device for protection against accidental contact.
The switch must be positioned in the immediate vicinity of the machine in
compliance with local accident prevention regulations.
Power cables must have a suitable section for absorbing current, without
deviations for other utilities.
Electric systems must be created according to the state of the art by a
qualified electrician who will check the earthing system’s efficiency.
The power cable must be locked in the dedicated cable gland and the
electric panel must be carefully closed to assure the envisaged IP 54
protection.
Only connect the machine to type approved sockets with an earth cable
of proven efficiency.
Periodically have qualified personnel check the correct tightening of the
electric cables of the various components.
8.2.1. Connection Instructions
The supply electrical cable comply with the
standard and is made by four wires of adequate
section.
Attention:
power the lift's electrics system using a line fitted with a mains switch
and without any other junctions.
The devices fitted to provide protection against short circuits must
take into account the features of the electrical equipment:
NOMINAL POWER
kW
2,5
2,5
VOLTAGE
V
230
400
No. of phases
3
3
FREQUENCY
Hz
50
50
NOMINAL CURRENT
A
13
6,4
PICKUP CURRENT
A
91
35,8
PROTECTION
FUSE (DELAYED)
A
20
10
FUSE (FAST)
A
25
20
THERMOMAGNET
A
25
25
CABLE SECTION
mm
2
2.5
2.5