OMEGA-VSHPe.F-IOM-2205
14
This mode is disabled during the recycled air defrost mode.
ERV FAN SETTINGS
ERV Fan Setting
The ERV fans are factory set to default position. It is recommended to perform an air balance to determine required
fan speeds
-
Low and High. The potentiometers located on the ERV board controls the Low and High fan speeds.
These speeds are controlled using a PWM signal from 0% to 95% Torque. The range of the potentiometer is 8
o
’
clock to 4 o
’
clock.
High Speed
Potentiometer
Speed Switch
Low Speed
Potentiometer
Rotate clockwise to
increase fan speed,
rotate counterclock-
wise to reduce fan
speed.
ERV Fan Performance
0.00
0.025
0.05
0.075
0.10
0.15
0.20
0.25
0.30
0.40
0.50
25% Speed @ 6 Watts
10 O'clock
43
34
28
22
18
12
-
-
-
-
-
37% Speed @ 13 Watts
11 O'clock
70
54
43
34
27
15
7
-
-
-
-
45% Speed @ 18 Watts
12 O'clock
85
67
55
44
35
23
15
-
-
-
-
57% Speed @ 30 Watts
1 O'clock
111
95
83
74
68
54
45
37
30
21
15
69% Speed @ 43 Watts
2 O'clock
139
124
114
106
104
91
82
73
63
53
44
82% Speed @ 61 Watts
3 O'clock
168
155
150
141
139
127
119
107
96
85
72
95% Speed @ 82 Watts
4 O'clock
187
172
166
157
156
145
137
124
115
105
91
ESP (External Static) inwg
% PWM Signal / Power
Potentiometer
Dial Setting
Notes:
•
All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).
•
ERV external static setting is based on exhaust duct run.
•
ESP capability shown per fan.
•
Recommended ERV fan speeds are field set to match duct static. Default factory settings may not match site conditions and
requirements.
•
Watts includes both ERV fans.
•
Internal Manual OA Slider Damper may be used to control OA introduction in the event of variable OA conditions (i.e. wind stack
effect)