Troubleshooting Guide : Chassis Low Voltage Controls
Troubleshooting Low Voltage Chassis Controls
Troubleshoot chassis low voltage using the low voltage chassis harness without the need to pull out chassis or re-
move chassis top cover. Check resistance readings using a multi
-
meter probe to confirm continuity across: safeties
(HPS, LPS), sensors (EWT, LWT, RST) and valves (ASOV, REV).
HPS
-
High Pressure Switch:
•
Check continuity between that switch is Normally Closed.
LPS
-
Low Pressure Switch
•
Check continuity between that switch is Normally Closed.
RST
-
Refrigerant Suction Temperature Sensor
•
Check resistance for 10KOhm sensor across RST and Common (white).
EWT
-
Entering Water Temperature Sensor
•
Check resistance for 10KOhm sensor across EWT & Common (white).
LWT
-
Leaving Water Temperature Sensor
•
Check resistance for 10KOhm sensor across LWT & Common (white).
REV
-
VALVE
-
Reversing Valve Solenoid
•
Check for short to ground faults.
2
-
Way ASOV
-
2
-
Way Zone Valve
•
Check for short to ground faults.