Digital I/O and Relays
Use the provided terminal block connectors and the connector
diagram in Figure 5 to wire Digital I/O and Relays to the iServer 2.
The DI connections (DI2+, DI2-, DI1+, DI1-) accept a 5 V (TTL) input.
The DO connections (DO+, DO-) require an external voltage and
can support up to 0.5 amps at 60 V DC.
The Relays (R2, R1) can support a load of up to 1 amp at 30 V DC.
Important:
When wiring the included terminal block
connectors to access the digital I/O, alarms, or
relays, it is recommended that users ground the unit
by connecting a wire to the chassis ground of the
connectors shown in Figure 9.
Below is an example of an LED Circuit connected to the Digital Inputs and outputs.
Figure 10: iServer 2 sample LED circuit with digital input and output
Further configuration regarding Normally Open/Normally Closed Initial State or Triggers can be
completed in the iServer 2 web UI. For more information, refer to sections 6.5.2 Relay 1 and Relay 2
or 6.5.4 Digital I/O.
Figure 9: iServer 2 Digital I/O and
Relays terminal block