3.2.9 Reading Adjust Menu
Figure 3.7 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
R.ADJ
Reading Adjust Menu.
READING ADJUST VALUE SUBMENU:
Press
d
4)
Display flashes 1
st
digit of previous Reading Adjust value.
Press
b
&
c
5)
Press
b
and
c
buttons to enter a new Reading Adjust value
(-1999 to 9999).
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
SP.DV
Setpoint Deviation Menu.
Reading Offset Adjust allows the user to fine tune a minor error of the transducer,
however some applications may require a large offset adjust. (Displayed Process
Value = Measured Process Value ±R.ADJ). Reading Adjust value is adjustable
between -1999 to 9999.