Section 3 – Electrical Connection and Temperature Measuring
Range Selection
All electrical connections and wiring should be performed by a
suitably trained professional only.
3.1 Electrical Connection
Follow the electrical connection diagram shown in figure 3-1 below to set up
your Temperature/Relative Humidity Transmitter.
Figure 3-1 Electrical Connection Diagram
3.2 Temperature Measuring Range Selection:
The temperature measuring range of the HX93B can be modified by making
a minor change to a connector J4. The standard temperature measuring range
is -30 to 75°C (-22 to 167°F) without adding any jumper on connector J4. If
you would like to change the range to -20 to 75°C (-4 to 167°F), add a jumper
on connector J4 pin 1 to pin 2. See the diagram below for the location of the
connector and its pins.
Figure 3-2 Temperature Measuring Range Selection Diagram
3-1
Electrical Connection and
Temperature Measuring Range Selection
3
POWER IN
R/H OUTPUT
TEMPERATURE OUTPUT
GND
GND
CHASSIS
1
2
3
4
5
6
+
+
–
–
+
–
POWER SUPPLY
9-30 VDC
(12-30 VDC FOR
0-10 VDC OUTPUT)
4-20 mA
0-1 VDC
0-5 VDC
0-10 VDC
TB1
INTERNALLY
CONNECTED
TEMPERATURE MEASURING
RANGE SELECTION
CONNECTOR
8-PIN M12 CONNECTOR
FOR DIGITAL SENSOR PROBE
1
3
J4
°F
°C
J5
NOTE: