Installation of FMG90B 

FMG90B Series 

- 10 - 

 

 

 

 

  Installation can occur in horizontal and vertical pipes. The flow sensor is only suitable for 

application in completely filled pipe systems. 

  As a matter of principle magnetic inductive flow sensors are widely independent from the 

flow profile. An inlet section is not absolutely necessary. 

To reach a most highly accuracy of the measurement, you should use straight inlet and 

outlet sections according to the inner diameter. The inlet section has to be at least 

10 x inner diameter; the outlet section 5 x inner diameter in order to achieve the specified 

accuracy. 

  The inlet and outlet sections and the gaskets must have the 

same or a slightly larger inside diameter than the measuring 

tube in order to achieve the specified accuracy. 

  If two or more FMG90B devices are used side by side, 

maintain a separation of at least 1.0 in between adjacent 

devices. 

If adjacent devices are too close together, operation of both 

devices may be impaired due to mutual interference.  

 

 

4.2  Assembly 

The FMG90B is installed directly into the pipeline. The compact design and light weight of the 

unit make wall-mounting unnecessary. 

 

IMPORTANT NOTICES: 

• Only use suitable gaskets for installation. 

• Observe the flow direction indicated on the type plate.  

• Observe the mounting dimensions (

 § 9.3 “Dimensions”). 

 

  Select an appropriate location for installation 

(

 § 4.1 "Installation instructions").  

To ensure the best possible measuring accuracy, a vertical 

installation position with increasing flow is preferable (no 

collecting of dirt deposits). 

  Wrap the FMG90B connections with 1 to 2 wraps of thread 

tape (e.g. Teflon

®

 tape). Wrap tape in a clockwise direction, 

viewed form the end, leaving the first two threads uncovered. 

  Make sure the tape does not intrude into the flow path.  

  Attach the FMG90B with arrow pointed in the direction of flow.  

  The fittings should be screwed into FMG90B hand tight.  

 

 

CAUTION! Material damage!  

Maximum torque 3.7 ft lb. 

While tightening, counter the FMG90B only by hand! 

If you use an open-end or a pipe wrench, the FMG90B can 

be damaged. 

 

 

  To tighten the FMG90B, use an open-end or a pipe wrench 

for the fittings and only the hand for the FMG90B. 

 

 

 

 

 

 

Summary of Contents for FMG90B Series

Page 1: ...Electromagnetic Flow Meter FMG90B Series...

Page 2: ...2...

Page 3: ...d measuring operation 13 6 1 Commissioning 13 6 2 Switching on and off 13 6 3 Measuring operation 13 7 Maintenance and cleaning 14 8 Disassembly and disposal 15 9 Technical data 16 9 1 Characteristics...

Page 4: ...ngers that cause personal injuries that can lead to health defects or cause considerable damage to property CAUTION Electric current This sign indicates dangers which could arise from handling of elec...

Page 5: ...its have been carefully checked for their operational reliability before shipment Immediately after receipt please check the outer packaging for damages or any signs of improper handling Report any po...

Page 6: ...ces be exceeded Before installing the device check that the wetted materials of the device are compatible with the media being used 9 Technical data Measuring tube empty or partially filled Conductivi...

Page 7: ...must be aware of this operating manual and have access to it at all times The electrical connection should only be carried out by a fully qualified electrician General safety instructions In all work...

Page 8: ...dle of the measuring tube between the grounding sleeves The FMG90B does not need any moving parts to make measurements The inside of the measuring tube is completely open allowing the fluid to flow un...

Page 9: ...ITABLE TOOLS Use only suitable tools of the correct size 4 1 Installation instructions CAUTION Risk of malfunction due to external magnetic fields Magnetic fields close to the device can cause malfunc...

Page 10: ...due to mutual interference 4 2 Assembly The FMG90B is installed directly into the pipeline The compact design and light weight of the unit make wall mounting unnecessary IMPORTANT NOTICES Only use sui...

Page 11: ...UTION Electric current The electrical connection should only be carried out by a fully qualified electrician De energize the electrical system before connecting the FMG90B Connection cable Suitable co...

Page 12: ...e Supply voltage FMG90B with frequency output Push Pull NPN Open Collector PNP Open Collector 1 Push Pull switching outputs of several FMG90B may not be connected in parallel 2 Recommendation Pull Up...

Page 13: ...voltage Switch on the supply voltage The green LED lights up The FMG90B is ready and goes into measuring mode 6 3 Measuring operation In the measuring mode the green LED flashes proportional to the me...

Page 14: ...of a defect the device must be replaced or sent back the manufacturer for repair CAUTION Material damage When opening the device critical parts or components can be damage Never open the device and pe...

Page 15: ...re disassembly Prior to disassembly ensure that the equipment is switched off and is in a safe and de energized state the equipment is depressurized and has cooled down Disassembly Remove the electric...

Page 16: ...tion ml pulse 0 1 0 25 1 0 2 5 5 0 12 5 Signal shape Square wave signal duty cycle 50 50 Push Pull NPN open collector PNP open collector Signal current 100 mA Electrical characteristics Supply voltage...

Page 17: ...als table Component Material Component wetted Housing ABS Measuring tube POM or PVDF option X Process connections POM or PVDF option X O ring EPDM or FKM option X Electrodes and grounding rings Stainl...

Page 18: ...FMG98B 0 0 0 5 1 0 1 5 2 0 2 5 3 0 0 0 1 0 2 0 3 0 4 0 5 0 6 Pressure drop p psi Flow rate Q GPM US version 0 0 0 5 1 0 1 5 2 0 2 5 0 0 25 0 5 0 75 1 1 25 1 5 Pressure drop p psi Flow rate Q GPM 0 00...

Page 19: ...915B FMG920B FMG925B 0 000 0 125 0 250 0 375 0 500 0 2 4 6 8 10 12 14 Pressure drop p psi Flow rate Q GPM 0 0 0 5 1 0 1 5 2 0 0 10 20 30 40 50 Pressure drop p psi Flow rate Q GPM 0 0 0 1 0 2 0 3 0 4 0...

Page 20: ...20 9 4 Dimensions FMG90B FMG96B Type L1 L2 D1 D2 FMG93B 3 35 0 51 NPT 0 12 FMG96B 3 35 0 51 NPT 0 31 x 0 08 FMG98B 3 35 0 51 NPT 0 31 FMG915B 3 54 0 63 NPT 0 55 FMG920B 3 54 0 63 1 NPT 0 71 FMG925B L1...

Page 21: ...FMG90B Series For your notes Technical changes reserved 21 For your notes...

Page 22: ...For your notes FMG90B Series 22 For your notes...

Page 23: ......

Page 24: ...M5759 0220...

Reviews: