background image

1

    DESCRIPTION & SPECIFICATIONS

DESCRIPTION:

The OMEGA DPF70 is a dual input (channel A and B) counter/
ratemeter, each with its own 5 digit dividing scale factor.  The two 5
AMP preset relay outputs can be programmed by the user to apply
to the "A" total counter, the "A" ratemeter, or the "B" counter or the
net total of A and B inputs.  The user can view the Net Total of
"A+B", the Net Total of "A-B", the rate of A, or A and B counters
separately.  The "DPF75" version shows rate and total (as de-
scribed above).  The "DPF76" is exclusively a counter and the
"DPF78" is exclusively a ratemeter.

SPECIFICATIONS:
DISPLAY

6 digit, 0.55" High LED

INPUT POWER:

110 VAC 

±

 15% or 11 to 15 VDC

220 VAC 

±

 15% or 11 to 15 VDC

CURRENT:

250 mA DC max. or 6.5 VA  AC

OUTPUT POWER 

 (AC powered units only)

+12 VDC @ 50 mA, unregulated -10 + 50%

TEMPERATURE:

Operating: +32

°

F (0

°

C) to +130 F (+54

°

C)

Storage: -40 F (-40

°

C) to +200

°

F (93

°

C)

DIMENSIONS:

 See next page.

WEIGHT:

2 Lbs. (1 kg)

MEMORY

EEPROM stores data for 10 years if power is lost.

INPUTS:

3:

High Impedance DC pulse input Open or 0-1 VDC
(low), 4-30 VDC (high), 10 KOhm imp. 10 KHz max.
speed. Accepts simultaneous inputs.

3M:

Mag. Input, Input A only, accepts 30mV input (50 V max. P/P)
signals 10 KOhm imp. 5 KHz max. (Input B, 4-30V)

3MB: Mag. Input, Inputs A & B, accepts 30mV input (50 V max. P/P)

signals 10 KOhm imp. 5 KHz max.

5:

4-30 V Count pulses on Input A, 4-30 V Direction
Control input (level) on Input B.

5M:

30 mV Count pulses on Input A (50 V max. P/P)
4-30 V Direction Control input (level) on Input B

9:

Quadrature, accepts 4-30 V pulses with 90

°

phase

shift for direction detection.

9MB: Quadrature, accepts 30 mV (50 V max. P/P) pulses with

90

°

phase shift for direction detection.

NOTE:

 The Mag. inputs have filtering as follows:  up to 300hz

@30mV, 5KHz @ .25V to 50V max.

RESET:

Front Panel:

Resets displayed value and control output

Remote:

4-30 VDC negative edge resets COUNTER "A" and control
output

K FACTOR/SCALING

In the standard unit a fixed K-Factor is used to convert the input
pulses to engineering units.  The 5 digit K-Factor dividers, with
decimal keyed into any position, allow easy direct entry of any K-
Factor from 0.0001 to 99999.  Separate factors may be entered for
the 2 separate input channels.

CONTROL OUTPUTS:

Relays:

2 each N.O. Relay; 5 Amps120/240 VAC or 28 VDC.
(N.C. relay contacts and NPN transistor output
available with solder jumpers.  Transistor output is
internally pulled up to 10 VDC through relay coil, sinks
from 10 VDC to .5 V @ 100 mA)

Analog Output:

An optional 4-20mA (0-20mA) output is available for
the DPF70 series.  The output can be programmed
to track rate or total.  This feature is available by
adding suffix A to the part number.  Connections are
via a 2 terminal pluggable screw connector.
Programming is accomplished by using the front panel
in conjunction with rear dip switches.
Accuracy: 50uA worst case.
Compliance Voltage: 3 to 30 VDC non inductive.

RS232/RS422SERIAL INTERFACE

If the serial interface option is supplied, up to 99 units can be linked
together. (The terminal addressing the unit must be capable of
driving all loads in the loop.)  Unit status and new set points can be
communicated by serial communication. Mode changes, however,
must always be made on the front panel. Data is transmitted at
selected baud rates using standard seven bit ASCII characters and
parity with two additional bits of “Start” and “Stop” to make up the
standard ten bit character.
Data is received and transmitted over standard EIA RS232 or
RS422 levels. Each 10 bit character is made up of a start bit, 7 bit
ASCII code, parity bit and stop bit. Unit number, baud rate and
parity are entered in the “Program Setting” set up mode and remain
in memory even if power is off.
Note that the input impedance of RS232 is 3K or 7K Ohm worst
case. The terminal addressing the unit must be capable of driving
all loads in the loop. RS422 input impedance is much higher and
there is usually no problem driving 25 units. Unit serial transmit line
remains in a high impedance “OFF” state until addressed.

PRESETS

Two control outputs are provided.  To set relay values, press “menu”
button until “Relay” appears on  the display, the A and B outputs
can be assigned to the ratemeter (high/low), one preset for rate
and one for total, or two presets (2 stage shut off) on the A and B
counters.  A 5 digit value can be entered for both presets and the
decimal point location is the same as the counter.  The outputs can
be set to energize from 0.1 to 99.9 seconds or latch (0.0).  If a value
other than 0.0 is entered, the counters will auto reset at the preset .
In the A-B or A+B versions, the relays will be assigned to either net
total or A rate.

LOCKOUT

Unauthorized front panel changes can be prevented by entering a
user selected 5 digit code, in the “LOC” , . mode.  The front panel
can be completely locked out or the presets can remain accessible.

RATEMETER

Accurate to 4 1/2 digits (

±

1 display digit).  The rate meter can be

programmed to accept almost any number of pulses per unit of
measurement, sample from 2 to 24 seconds maximum, and auto-
range up to 5 digits of significant information.  In the “RPS” mode,
the ratemeter displays in units per second, and in the “scale” mode,
units per hour or per minute. The unit will display the rate of the A
Input only.

COUNTER

The two 6-digit counters can count at 10Khz speed.  Each can
have a 5-digit dividing scale factor.  The counter advances on the
positive edge of each pulse.  Count up or down modes available, as
are quadrature inputs from encoders for position or length mea-
surement.  The unit can be programmed to view the net value of
"A+B" or "A-B", or A  and B as separate counters.

Summary of Contents for DPF78 SERIES

Page 1: ...www omega com e mail info omega com User sGuide DPF75 DPF76 AND DPF78 SERIES Rate Totalizer Shop online at M1090 071603...

Page 2: ...33 0 130 621 400 FAX 33 0 130 699 120 Toll Free in France 0800 4 06342 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 9398 0 FAX 49 0 7056 9398 29...

Page 3: ...E UNIT 13 SETTING THE RELAYS PRESETS 14 OUTPUT WIRING 15 ANALOG OUTPUT OPTION 16 RS232 RS422 SERIAL COMMUNICATIONS 17 RS232 RS422 WIRING 19 TROUBLESHOOTING GUIDE 20 UNPACKING Remove the Packing List a...

Page 4: ...rate batch and grand total The PRE A PRE B keys allow you to see and set the relay trigger points The lock key allows you to lock and unlock the keypad functions by entering the lock out code The PRO...

Page 5: ...unlock RELAYS STEP 5 DPF75 The DPF76 relays can only trigger on batch or total The DPF78 relays can only trigger on rate The DPF75 relays can be programmed to trigger on rate or total The relay setpoi...

Page 6: ...ramming is accomplished by using the front panel in conjunction with rear dip switches Accuracy 50uA worst case Compliance Voltage 3 to 30 VDC non inductive RS232 RS422SERIAL INTERFACE If the serial i...

Page 7: ...s than 125 of an inch thick the possibility exists that there will be some flexing Should this flexing occur the resulting deformation of the panel could cause a loss of the water tight seal In case t...

Page 8: ...ably at the D C ground terminal of the unit 3 Output lines The unit has two relay outputs When these outputs are used to run external relays or solenoids spikes can be generated upon activation This n...

Page 9: ...ons FTB600 Flow Meters Brown 1 COMMON 2 N O N C NPN 3 COMMON 4 N O N C NPN 5 A INPUT 6 B INPUT 7 11 to 19V 50mA OUT DC IN 8 DC GROUND 9 RESET INPUT 10 6 to 14V 50mA 11 A C INPUT 12 A C INPUT RELAYS A...

Page 10: ...l is being displayed See below on how to modify for Batch Count and B as a Grand Total Counter MILLIVOLT INPUT OPTION JUMPER SELECTIONS OUTPUT JUMPER SELECTIONS FUNCTION A RELAY N C OUTPUT B RELAY N C...

Page 11: ...LOWCHART NOTE Several programming selections will not appear with DPF76 and DPF78 units PRGM Press this key to step through menu choices ENTER RST Press this key to enter displayed value Start Here DP...

Page 12: ...A B INPUTS ARE SEPARATE A B are not added or subtracted A SUB B A SUBTRACT B The number of scaled pulses from Input B are subtracted from the number of scaled pulses from Input A 99999 TO 999999 A AD...

Page 13: ...reset A when in A NET B or A SEP B mode The relay will drop out when the rate of A falls below preset A A RELAY A DURATION This message will appear when A TOT is selected It is the duration which the...

Page 14: ...readout Solution Enter a Factor of 10 and for every 10 pulses 1 will appear on the display Set rate per second minute or hour as desired A conveyor carrying bottles must be controlled for bottle speed...

Page 15: ...TE only version Press the PRGM key to choose HIGH CPS 0 9 99KHz or LOW CPS 0 40Hz Press the ENTER key to enter the displayed choice This sets the decimal for factor B Press the arrow key under the dig...

Page 16: ...imal location for the A B counters Press the arrow key under the desired digit location To clear the decimal press the arrow key furthest to the right Press the ENTER key to enter the displayed loca t...

Page 17: ...ys under the desired digits to change Press ENTER to enter displayed value This sets the number of significant figures to be displayed Press the arrow key under the digit to change Press ENTER to ente...

Page 18: ...ce After CODE flashes the display will show the existing lock code To change the code press the key under each digit to be changed Press ENTER to enter displayed value Key in the lock code see program...

Page 19: ...This is the duration 1 to 99 9 sec that relay B will remain energized If 00 0 is selected the relay will latch until reset PRE A Preset A Final Preset The set point at which output A will trigger If t...

Page 20: ...atch is complete or the rate has exceeded a set speed The outputs are programmable to be assigned for rate or count When assigned to the count the relays can have a user selectable on time duration or...

Page 21: ...2 Select Count or Rate SW2 OFF down Analog output follows rate SW2 ON up Analog output follows count SWITCH 3 Select 4 20mA or 0 20mA SW3 OFF down Selects 4 20mA output range SW3 ON up Selects 0 20mA...

Page 22: ...e is pressed PARITY Parity is a bit of information that is inserted before the stop bit and is used to help check if the transmission is correct When setting the parity you may select ODD parity bit i...

Page 23: ...ssing the unit must be capable of driving all loads in the loop The input impedance of RS422 is much higher and there should be no problem driving as many as 99 units The transmit line remains in a hi...

Page 24: ...PIN 7 STROBE PIN 6 12V PIN 7 BOTTOM BOARD A RST B C D E ENTER LOCK PRE A PRE B VIEW PRGM TRANSMIT PIN 2 GROUND PIN 5 RS 232 STROBE PIN 6 12V PIN 7 BOTTOM BOARD RS232 RS422 WIRING A RST B C D E ENTER...

Page 25: ...the units with rate and total DPF75 When using a unit which has only count DPF76 or only rate DPF78 several menu items will not be displayed 1 Recheck power wiring 1 Use a different power supply or in...

Page 26: ...21 NOTES...

Page 27: ...22 NOTES...

Page 28: ...23 NOTES...

Page 29: ...shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA...

Page 30: ...Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH...

Reviews: