4
Configuring The Meter
32
4.7 USING SETPOINT 2 CONFIGURATION
S2.CF
Refer to Table 6-1 for a summary list of menu configuration.
Setpoint 2 Configuration
S2.CF
is not active unless your meter has dual relay output
capabilities. The LED's will display whether the
S2.CF
is active or not. You may use
Setpoint 2 Configuration
S2.CF
for the following:
• To set the setpoint's active band above or below your chosen value
• To select whether the setpoint operation is latched or unlatched
4.7.1 Setting Setpoint 2's Active Band
1.
Press the
MENU
button until the meter shows
S2.CF
.
2.
Press the
∂
TARE
button. The meter shows one of the following:
•
S.1=A
(Active above the setpoint)
(Default)
•
S.1=B
(Active below the setpoint)
3.
Press the
ß
MAX
button to toggle between available choices.
4.
Press the
∂
TARE
button to select if Setpoint 2 is latched
or
unlatched or press
the
MENU
button to store your selection and enter
S1.DB
(Setpoint 1 Deadband)
4.7.2 Selecting if Setpoint 2 is Latched or Unlatched
1.
Press the
MENU
button until
S2.CF
displays, then press the
∂
TARE
button twice.
or
Press the
∂
TARE
button from
S.1
.
The meter shows one of the following:
•
S.2=U
Setpoint 2 to be unlatched
(Default)
•
S.2=L
Setpoint 2 to be latched
2.
Press the
ß
MAX
button to toggle between available choices.
3.
Press the
MENU
button to store your selection(s). The meter momentarily shows
STRD
, followed by
S1.DB
(Setpoint 1 Deadband).