41
Configuring The Meter
4
41
4.13 USING OUTPUT SCALE AND OFFSET
OT.S.O
Refer to Table 6-1 for a summary list of menu configuration.
Output Scale and Offset
OT.S.O
is not active unless your meter has analog output
capabilities. The menu will display whether analog output is present or not. Output Scale
and Offset
OT.S.O
scales your analog output to be equal to the meter's display and/or
any engineering units you require. You may scale the output for direct (4-20 mA, 0-10 V,
etc) or reverse acting (20-4 mA, 10-0 V, etc).
1.
Press the
MENU
button until
OT.S.O
displays.
2.
Press the
∂
TARE
button.
RD1
(Read 1) displays.
This is your first point of display reading.
3.
Press the
∂
TARE
button again. The meter shows the last previously stored
4-digit number (-1999 through 9999) with flashing 4th digit.
4.
Press the
ß
MAX
button to change the digits.
5.
Press the
∂
TARE
button to scroll to the next digit.
6.
Press the
MENU
button to store your selection.
OUT.1
(Output 1) displays.
This starting analog signal corresponds to your Read 1 display.
7.
Press the
∂
TARE
button. Selected output displays.
If you select
O.2=V
for voltage, the maximum signal you may select is
10.00 for an 0-10 Vdc signal output. If you select
O.2=C
for current, the
maximum signal you may select is 20.00.
8.
Press the
ß
MAX
button to enter the Output 1 signal selection. If you continue to
press the
ß
MAX
button, the flashing digit's value continues to change.
9.
Press the
∂
TARE
button to scroll to the next digit.
10.
Press the
MENU
button to store your selection.
RD!2
(Read 2) displays.
This is your second point of display reading.
Note
☞
Note
☞
Note
☞
Note
☞
Note
☞