5.  HOW  TO  MAINTAIN,  CHECK    AND  SERVICE  BURNER.

  1)  CHECK  OF  BURNER.

▶  check  the  followings  prior  to  burner  operation.

        ①  after  checking  the  water  level  of  boiler,  pressure  and  fuel  feed  rate,  open  the   

              valve  between  tank  and  oil  pump.

        ②  check  whether  the  working  voltage  and  fuel  meet  the  burner  specification.

        ③  discharge  air  from  the  fuel  pipe  system.

        ④  check  whether  or  not  the  burner  nozzle  corresponds  the  boiler  or  furnace           

              capacity..

  ▶  maintenance  of  burner

        ①  clean    the  ignition  bar  if  it  is  contaminated.

        ②  clean  nozzle  and  nozzle  adapter.

        ③  if  soot  is  accumulated  on  the  diffuser,  burner  fails  to  ignite.

              remove  the  soot  from  the  diffuser.

        ④  check  and  clean  oil  filter  if  required.

        ⑤  check  and  clean  flame  detector  if  required.

Summary of Contents for LT-80

Page 1: ...OLYMPIA BURNER OPERATING MANUAL MODEL LT 40 45 60 80 100 120 150 200 250 300 400 500 600 700 OLYMPIA INDUSTRIAL CO LTD...

Page 2: ...TION SYSTEM 4 HOW TO INSTALL FUEL PIPE SYSTEM 5 TIME CHART 6 ELECTRIC CIRCUIT DIAGRAM 3 HOW TO USE MAJOR PARTS 1 COMBUSTION HEAD DIMENSION 2 HOW TO ADJUST COMBUSTION OF AIR FLOW RATE 3 HOW TO DISASSEM...

Page 3: ...214 HI MID LOW O FF or MODURATING 5 5 E 7 11 8 20 4 LT 300T 80 250 7 5 TA 2 PT 1 2 PT 1 2 15 8 27 3 LT 400T 108 330 11 20 4 35 5 LT 500T 136 408 11 20 4 35 5 LT 600T 194 583 15 20 4 35 5 LT 700T 167 6...

Page 4: ...2 COMBUSTION PERFORMANCE GRAPH...

Page 5: ...3 SIZE AND DIMENSION LT 40 45 60 DIMENSION...

Page 6: ...lled as follows depending on the number of nozzle two nozzle 2 position control hi low off three nozzle 3 position control hi mid low off one proportional nozzle proportional control modulating how to...

Page 7: ...4 EXPLODED DRAWING OF BURNER AND PART NAME 1 LT 40U 45U 60U BURNER EXPLODED DRAWING...

Page 8: ...2 LT 40UH 45UH 60UH BURNER EXPLODED DRAWING...

Page 9: ...3 LT 80U 100U 150 200 250 300 400 500 600 700 BURNER EXPLODED DRAWING LT 80T 100T 150 200 250 300 DAMPER MOTOR LT 250 300 400 500 600 700 3NOZZLE...

Page 10: ...400 D 228 228 315 350 430 430 E M10 M10 M14 M14 M16 M16 2 HOW TO CONTROL BURNER 1 BURNER COMBUSTION FURNACE DIMENSION 2 HOW TO INSTALL BURNER 1 burner assembly sequence refer to above sketch insert ga...

Page 11: ...bustion gas leaks after installing the hinge type burner use care so that no part of ignition bar is damaged or deformed during assembly of frame secure enough working space to check and maintain burn...

Page 12: ...plug when oil tank is below burner H its height must be less then 2 4m the inlet hole should place at 20cm higher then the floor of oil tank in order not to flow in foreign subtainces it is recommend...

Page 13: ...5 TIME CHART...

Page 14: ...6 ELECTRIC CIRCUIT DIAGRAM...

Page 15: ...MODURATING TYPE...

Page 16: ...1 COMBUSTION HEAD DIMENSION in case of adjusting C size be careful not to touch the and of ignition bar with diffuser or diffuser is not stained with oil 2 HOW TO ADJUST COMBUSTION AIR FLOW RATE 1 hyd...

Page 17: ...ustion then fully tighten the nut A second stage high combustion air adjustment loosen the nut D in the high combustion mode and tighten adjuster nut C to increase air flow rate until no smoke coming...

Page 18: ...iagram how to adjustment damper damper gauge consists of from 0 to 10 0 indicates complete close and 10 indicates complete open disconnect power adjust each CAM by deciding the position depending on t...

Page 19: ...he low combustion damper CAM when the s w is out of order replace the s w when it is completely closed use the manual adjuster knob to set in ti the low combustion opening position when pressing the h...

Page 20: ...acement b how to disassemble and check nozzle separate filter clean the filter using kerosene separate the gelical support using a screwdriver clean the groove using kerosene and thin wire do not use...

Page 21: ...conds after burner ignitions check whether there is a soot or dust on the flame sensor of the flame detector thoroughly remove soot or dust from the flame sensor if any if soot or dust is accumulated...

Page 22: ...asing 3 how to purge air from the pump turn the gear pump air purge bolt counterclockwise 3 to 4 times with spanner operate burner then air bubble comes through the air exhaust hole of the gear pump t...

Page 23: ...emergency operation only continue to check conditions of flame during manual operation high combustion valve on automatic operation by inter lock auction take care of the ignition transformer as high...

Page 24: ...oltage and fuel meet the burner specification discharge air from the fuel pipe system check whether or not the burner nozzle corresponds the boiler or furnace capacity maintenance of burner clean the...

Page 25: ...2 BURNER TROUBLE ACTION TABLE...

Page 26: ...raise discharge pressure discharge air check valve and clean filter replace and repair adjust damper replace and repair replace and repair replace and repair when combustion stop immediately after ig...