P  O  W  E  R

automatic  operation

manual  operation

burner  s/w  turns  on

burner  s/w  turns  on

auto/man  s/w  :  auto

auto/man  s/w  :  manual

lock  release

inter  lock  release

blower/gear  pump  operate

blower/gear  pump/  ignition  transformer  operation

operation  of  ignition  bar

low  combustion  s/w  :  on

low  combustion  valve  :  on

high  combustion  s/w  :  on

flame  detecter  check  the  ignition

hydraulic  cylinder  or  damper  motor  operates

hydraulic  cylinder  or  damper  motor  operates

safety  device  does  not  operate  in  the  manual  mode, 

use  manual  mode  for  emergency  operation  only. 

continue  to  check  conditions  of  flame  during  manual 

operation

high  combustion  valve  :  on

automatic  operation  by  inter  lock

☞  auction:  take  care  of  the  ignition  transformer  as  high  voltage  is  applied  to  the           

      ignition  transformer.

7)  FUEL  FILTER.

  ▶  how  to  handle  fuel  filter

 

․ 

the  fuel  filter  removes  foreign       

    substance  from  fuel.

 

․ 

when  burner  does  not  generate   

    flame  as  no  fuel  is  fed  even  if     

  oil  pipe  is  contained  in  the  fuel     

  tank,  clean  the  fuel  filter.

 

․ 

when  fulling  out  a  container  ③   

      below  the  plastic  cap①,  you       

    find  a  filter②  in  the  container.

 

․ 

clean  the  filter  using  kerosene     

      or  light  oil,  replace  filter.

 

◉ 

fully  tighten  the  filter  to  prevent  penetration  of  air  after  cleaning  the  filter.

4.  GENERAL  BURNER  OPERATION

Summary of Contents for LT-80

Page 1: ...OLYMPIA BURNER OPERATING MANUAL MODEL LT 40 45 60 80 100 120 150 200 250 300 400 500 600 700 OLYMPIA INDUSTRIAL CO LTD...

Page 2: ...TION SYSTEM 4 HOW TO INSTALL FUEL PIPE SYSTEM 5 TIME CHART 6 ELECTRIC CIRCUIT DIAGRAM 3 HOW TO USE MAJOR PARTS 1 COMBUSTION HEAD DIMENSION 2 HOW TO ADJUST COMBUSTION OF AIR FLOW RATE 3 HOW TO DISASSEM...

Page 3: ...214 HI MID LOW O FF or MODURATING 5 5 E 7 11 8 20 4 LT 300T 80 250 7 5 TA 2 PT 1 2 PT 1 2 15 8 27 3 LT 400T 108 330 11 20 4 35 5 LT 500T 136 408 11 20 4 35 5 LT 600T 194 583 15 20 4 35 5 LT 700T 167 6...

Page 4: ...2 COMBUSTION PERFORMANCE GRAPH...

Page 5: ...3 SIZE AND DIMENSION LT 40 45 60 DIMENSION...

Page 6: ...lled as follows depending on the number of nozzle two nozzle 2 position control hi low off three nozzle 3 position control hi mid low off one proportional nozzle proportional control modulating how to...

Page 7: ...4 EXPLODED DRAWING OF BURNER AND PART NAME 1 LT 40U 45U 60U BURNER EXPLODED DRAWING...

Page 8: ...2 LT 40UH 45UH 60UH BURNER EXPLODED DRAWING...

Page 9: ...3 LT 80U 100U 150 200 250 300 400 500 600 700 BURNER EXPLODED DRAWING LT 80T 100T 150 200 250 300 DAMPER MOTOR LT 250 300 400 500 600 700 3NOZZLE...

Page 10: ...400 D 228 228 315 350 430 430 E M10 M10 M14 M14 M16 M16 2 HOW TO CONTROL BURNER 1 BURNER COMBUSTION FURNACE DIMENSION 2 HOW TO INSTALL BURNER 1 burner assembly sequence refer to above sketch insert ga...

Page 11: ...bustion gas leaks after installing the hinge type burner use care so that no part of ignition bar is damaged or deformed during assembly of frame secure enough working space to check and maintain burn...

Page 12: ...plug when oil tank is below burner H its height must be less then 2 4m the inlet hole should place at 20cm higher then the floor of oil tank in order not to flow in foreign subtainces it is recommend...

Page 13: ...5 TIME CHART...

Page 14: ...6 ELECTRIC CIRCUIT DIAGRAM...

Page 15: ...MODURATING TYPE...

Page 16: ...1 COMBUSTION HEAD DIMENSION in case of adjusting C size be careful not to touch the and of ignition bar with diffuser or diffuser is not stained with oil 2 HOW TO ADJUST COMBUSTION AIR FLOW RATE 1 hyd...

Page 17: ...ustion then fully tighten the nut A second stage high combustion air adjustment loosen the nut D in the high combustion mode and tighten adjuster nut C to increase air flow rate until no smoke coming...

Page 18: ...iagram how to adjustment damper damper gauge consists of from 0 to 10 0 indicates complete close and 10 indicates complete open disconnect power adjust each CAM by deciding the position depending on t...

Page 19: ...he low combustion damper CAM when the s w is out of order replace the s w when it is completely closed use the manual adjuster knob to set in ti the low combustion opening position when pressing the h...

Page 20: ...acement b how to disassemble and check nozzle separate filter clean the filter using kerosene separate the gelical support using a screwdriver clean the groove using kerosene and thin wire do not use...

Page 21: ...conds after burner ignitions check whether there is a soot or dust on the flame sensor of the flame detector thoroughly remove soot or dust from the flame sensor if any if soot or dust is accumulated...

Page 22: ...asing 3 how to purge air from the pump turn the gear pump air purge bolt counterclockwise 3 to 4 times with spanner operate burner then air bubble comes through the air exhaust hole of the gear pump t...

Page 23: ...emergency operation only continue to check conditions of flame during manual operation high combustion valve on automatic operation by inter lock auction take care of the ignition transformer as high...

Page 24: ...oltage and fuel meet the burner specification discharge air from the fuel pipe system check whether or not the burner nozzle corresponds the boiler or furnace capacity maintenance of burner clean the...

Page 25: ...2 BURNER TROUBLE ACTION TABLE...

Page 26: ...raise discharge pressure discharge air check valve and clean filter replace and repair adjust damper replace and repair replace and repair replace and repair when combustion stop immediately after ig...