4) FLAME DETECTOR.
① the flame detector detects the igniting
conditions of burner. when it detects that
ignition fails, it stop burner operation as a
safety device.
② when burner stops operation in several
seconds after burner ignitions, check
whether there is a soot or dust on the flame
sensor of the flame detector. thoroughly
remove soot or dust from the flame sensor if
any.
◉
if soot or dust is accumulated on the flame sensor of the flame detector, burner
stops operation. therefore it is required to clean the flame sensor using clean dry
cloth every month.
5) GEAR PUMP.
(1) external drawing and specification.