background image

18

Start-Up And Adjustment Of Oil Burner

NOTE: Bacharach or Dwyer test kits include these 

instruments.

(See oil burner instructions for nozzle and electrode setting)

1. 

Verify oil burner nozzle is tight in adapter. Burner 

mounting bolts should be tight.

2. 

Check electrode setting, may have been jarred out of 

position during transportation.

3. 

Lubricate burner motor if necessary.

4. 

Set room thermostat to call for heat, or jump 

thermostat contacts on boiler control.

5. 

Open all oil line valves.

6. 

Turn service switch on. Burner will start.

7. 

On one pipe fuel systems only, bleed pump as soon as 

burner starts. Allow oil to run until all traces of air in 

suction line disappear.

8. 

Turn “OFF” burner and install pressure gauge port on 

pump.

9. 

Start burner and check oil pressure for 140 psi adjust if 

necessary.

Table 7   Oil Burner Settings

Boiler 

Model No.

Head 

Type

Static 

Disc

Air Band 

Settings

Air Shutter 

Settings

Nozzle Furnished

Pump Pressure 

(psi)

0BC3095

F3

2¾ 

U

0

6

Delevan 0.85x 80°B

140

0BC4100

F3

2¾ 

U

0

7

Delevan 0.85x 80°B

140

0BC4115

F6

2¾ 

U

0

6

Delevan 1.00x 80°B

140

NOTES:
Information in above table uses Beckett model AFG burner for both model numbers OBC-3 and OBC-4.
OBC4115 is rerated boiler which requires rerate kit.

Check safety control circuit

 after burner adjustments 

have been made for satisfactory  performance.

A.  High limit control: remove cover and note 

temperature setting. 

See  Figure 20, Page 17 

. With 

burner operating, decrease setting to minimum 

point.  When boiler water temperature exceeds set 

point, high limit switch will open, shutting off power 

to oil burner.  Return setting to desired high limit 

point.  Burner should start. 

B. Verify Primary Control and Flame Sensor -

• Flame Failure

 - simulate by shutting off oil supply 

with hand valve while burner is on. Sixty seconds after  

fl

 ameout, safety switch locks out, ignition stops, motor 

stops and oil valve - when used - closes. To restart, 

open oil supply valve and reset safety switch.

• Ignition Failure

 - With burner off, close oil supply 

valve and run through start-up procedure. Safety 

switch should lock out as in 

fl

 ame failure.

• Power Failure

 - Turn off main power supply switch 

while burner is operating. When burner stops, restore 

power and burner should start. If operation is not as 

described as above, check wiring and controls.

OPERATING INSTRUCTIONS

Burner Operation Instructions

• Use provided ¼" diameter slot in inspection cover plate 

to take draft readings in combustion chamber. 

See 

 Figure 20, Page 17 .

• Drill  ¼" diameter hole in 

fl

 ue pipe between boiler and 

barometric damper (if used) to take draft, CO

2

, smoke 

and temperature readings. Plug hole when done.

• Adjust air shutter on oil burner to obtain “trace” of 

smoke. Measure CO

at this point. 

• Increase air adjustment to lower CO

approximately one 

percent. 

• Verify minimum negative .02 w.c., (water column), 

“over

fi

 re” draft and zero smoke. 

• If -.02 w.c. “over

fi

 re” draft can not be maintained, 

changes and/or modi

fi

 cations may be required in venting 

or chimney.

• See table below as guideline for initial start-up. Make 

fi

 nal adjustments using combustion instruments.

 WARNING

Boiler and venting installations shall be performed 

by a quali

fi

 ed expert and in accordance with the 

appropriate manual. Installing or venting boiler 

or other gas appliance with improper methods or 

materials may result in serious injury or death due 

to 

fi

 re or to asphyxiation from poisonous gases such 

as carbon monoxide with is odorless and invisible.

!

     

Summary of Contents for OBC II Series

Page 1: ...T IRON BOILER INSTALLATION OPERATION MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com P N 240009512 Rev A 04 2012 Models OBC3...

Page 2: ...nts may result in personal injury or loss of life TO THE OWNER Installation and service of this boiler must be performed by a qualified installer TO THE INSTALLER Leave all instructions with boiler fo...

Page 3: ...a to be heated select boiler on basis of its Heating Capacity 5 Nozzle listed for use with Beckett Burner 6 Electrical service to be 120 Volts 15 Amps 60 Hz STANDARD EQUIPMENT Crated Boiler Flush Jack...

Page 4: ...l base as near chimney as possible and centrally located with respect to the heat distribution system as practical Allow 24 inches in front top and right hand side for servicing and cleaning or removi...

Page 5: ...sectional area of the openings to which they are connected Table 5 COMBUSTION AIR REQUIREMENTS Minimum Opening Requirement BTU Hr Input Mbh Unconfined Area Confined Area Outside Inside Outside Combust...

Page 6: ...d each opening shall have a minimum free area 1 square inch per 2 000 BTU per hour total input rating of all appliances in the enclosed space See Figure 5 D When ducts are used they shall be of the sa...

Page 7: ...ng as suggested in Figure 6 When boiler is used in connection with refrigerated systems A Chilled medium MUST BE IN PARALLEL with boiler Figure 6 Boiler Used In Connection With Refrigerated System B U...

Page 8: ...t the system or condition of the installation Although this method of piping is not typically required for baseboard heating systems A This method is used to protect systems using radiant panels and t...

Page 9: ...9 CONNECTING SUPPLY AND RETURN PIPING Figure 9 Bypass Piping Option Used to Protect From Converted Systems With High Water Temperature Figure 10 Typical Installation With Circulators...

Page 10: ...10 CONNECTING SUPPLY AND RETURN PIPING Figure 11 Typical Installation With Valves Figure 12 Typical Installation With DHW...

Page 11: ...fety relief valve outlet and downstream of union if used Terminate pipe with plain end not threaded Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installatio...

Page 12: ...chimney performance Chimney should extend at least 2 ft above any portion of building within 10 ft See Figure 15 It should produce a 06 to 08 inch W C draft as measured with draft gauge between boiler...

Page 13: ...13 VENTING SYSTEM INSPECTION INSTALLATION P N 240005186 Rev 1 0 06 05 Figure 16 Final Placement Of Boiler With New Vent Safety Switch Installed...

Page 14: ...ended E Compression fittings on suction line often allows air to be drawn into fuel pump making it difficult to maintain oil pressure at the nozzle F Do not run overhead fuel lines from tank to oil bu...

Page 15: ...be installed on an inside wall about four feet above the floor 2 NEVER install a thermostat on an outside wall 3 Do not install a thermostat where it will be affected by drafts hot or cold pipes sunli...

Page 16: ...16 WIRING DIAGRAMS Figure 19 Wiring Diagram...

Page 17: ...ration Thermostat calls for heat Circulator turns on Limit checks boiler water temperature Burner ignition delayed until limit determines call for heat cannot be met by residual heat in boiler and hea...

Page 18: ...h limit point Burner should start B Verify Primary Control and Flame Sensor Flame Failure simulate by shutting off oil supply with hand valve while burner is on Sixty seconds after flameout safety swi...

Page 19: ...14 5 Disconnect oil line from burner Recommend replacing nozzle at start of each heating season Lubricate burner motor and circulator motor if required with few drops of good grade of light motor oil...

Page 20: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...

Reviews: