Installation dimensions and clearances
■
Install each heat detector as centrally as possible
in the room being monitored.
■
Only install the heat detector on jointless,
smoke-impervious ceilings.
■
Install the heat detector directly underneath the
ceiling surface.
■
Always install the heat detector horizontally (even
with sloping ceilings).
■
The distance between a heat detector and wall
must be minimally 50 cm and maximally 250 cm.
■
If the room to be monitored is very large, it may
be advantageous to install more than one heat
detector.
=
=
50 cm-250 cm
50 cm-250 cm