WX16 User Manual | 47
Memory Floating Point
Notes: Returned as 15 bit 2s complement with ±5% over/under range applied. Therefore, this must be
considered when scaling values to be displayed at the ModBus master. The following equation may be
used to determine a value for display.
Display Value = MODBUS Value [ (Span Value –Zero Value) 1.1] + {Zero Value – [(Span Value – Zero Value) .05]}
32767
Type Channel
First
Last
Read
FC
Write
FC Notes
Channel
Value
1-16
33001-16
n/a 4 n/a
15bit
2s
complement
w/±5% over/under range
Analog Output
Notes: 12 bit integer for Channel Reading value = 800 counts = zero value, 4000 counts = 100% value.
Type Channel
First
Last
Read
FC
Write
FC Notes
Channel 1-16
31001
31016 4 n/a
12bit
integer
Reading
Channel Status words contain configuration and status bits for a channel. They are as follows:
Type Channel
First
Last
Read
FC
Write
FC Notes
Channel Status 1-16
31017
31032
4
n/a
16bit integer
(see bit by bit definition below)
Alarm 1 Trip
bit0
1 = Low
0 = High
Alarm 1 Horn Drive
bit1
1 = On
0 = Off
Alarm 3 Type
bit2
1 = Level
0 = Fault
Alarm 2 Horn Drive
bit3
1 = On
0 = Off
Linearize
bit4
1 = On
0 = Off
Alarm 3 Trip
bit5
1 = Low
0 = High
Input
Marker
bit6
1 = Input
Marker
Detected
0 = Normal Mode
Channel Disable
bit7
1 = Disabled
0 = Enabled
Controller Channel
In Cal
bit8
1 = Local Cal Mode
0 = Normal Mode
ModBus Data Type
bit9
1 = 4 byte float
0 = 2 byte integer
reserved
bit10
reserved
reserved
reserved
bit11
reserved
reserved
Alarm 1 Latch
bit12
1 = Latching
0 = Non latching
Alarm 2 Latch
bit13
1 = Latching
0 = Non latching
Alarm 3 Latch
bit14
1 = Latching
0 = Non latching
Alarm 2 Trip
bit15
1 = Low
0 = High
Alarm status words are bits packed into 16 bit integer where lsb = channel 1 alarm status and msb = channel 16
alarm status.