5 Maintenance
5.1 Maintenance and care
Oilon and Lämpöässä heat pumps are highly reliable and easy to maintain. If the
system has been installed with care and in accordance with the instructions provided,
there is usually no need for maintenance.
It is recommended to check the following at least once a year:
● Fluid level in the filling bottle (if installed in the system's brine circuit).
Check
monthly in the first year.
Filling bottle ver. 1
● Brine circuit pressure (if a pressurized brine circuit is used). Guideline value: 1 bar.
● Brine circuit T strainer.
● For instructions, refer to section
Filling and bleeding the brine circuit
.
Annual inspection
According to rules and regulations by authorities, appliances with a refrigerant charge
greater than 6 kg must undergo annual leakage testing. Heat pumps with a 3–6 kg
refrigerant charge are hermetically sealed, and do not require annual inspection.
A periodic inspection service is available for our heat pumps. During each inspection,
the heat pump’s operation is checked step by step. Any observations will be recorded
in an inspection report and the necessary corrective measures (such as adjustments to
settings) will be taken. For more information about the service, contact your dealer.
5.2 Typical problems during operation
If you are unable to fix the problem based on the information below, it is advisable to
first contact your local dealer or the system installer.
Problem
Cause
Solution
The temperature in the storage
tank matches its setpoint;
temperature is sufficient.
No action required.
It has been less than 1 minute
since the compressor stopped.
No action required.
The compressor does not start.
Blown or tripped fuse.
Check the fuses in the building’s
or apartment’s distribution board.
M8011 2204EN
43 (70)
Summary of Contents for VSi 6-14
Page 1: ...M8011 2204EN 25 January 2022 Installation and operation manual VSi 6 14 VMi 6 17 ss Control...
Page 2: ......
Page 59: ...Dimensional drawings VSi 10VS14_2 VSI 1 ver 1 10VS14_2 VSI 2 ver 1 M8011 2204EN 57 70...
Page 60: ...Dimensional drawings VMi 10VMI141_2 VMI 1 ver 1 10VMI141_2 VMI 2 ver 1 58 70 M8011 2204EN...
Page 73: ......