The unit’s installation site should have a floor drain. The site’s floor should be inclined
so that any runoff from the unit leads towards the drain.
Place the unit on a stable, steady base that can carry the entire weight of the heat
pump and a full storage tank, see the tank volume in the technical data. Mount the unit
securely in a vertical position onto its own leveling feet. Level the machine using the
machine’s leveling feet.
Fire insulation is not required.
Space requirements
The minimum height of the heat pump is approximately 183 cm with the adjustable feet
installed. Note that transportation supports add approximately 8 cm to the full height of
the unit.
● Leave at least 70 cm of clearance in front of the unit.
● Leave at least 30 cm of clearance above the unit for the necessary connections.
V series space requirements ver. 1
Pos.
Item
GSHP
Ground source heat pump
Model
A
B
C
O
X
F
Y
VSi
50/500
50
500/50
700
1150
700
1300
VMi
50
50
500
700
1570
700
1420
2.4 Removing the packaging and inspecting the contents
1. Remove the plastic wrapping and corner padding from around the product.
2. Check that the heat pump has not suffered any damage during transit. If you detect
any damage,
notify the carrier immediately.
It is advisable to take photos of the
damage.
3. Check the delivery contents immediately. If there are accessories missing,
notify
the dealer within 5 days of delivery.
The heat pump’s accessory package includes the following:
12 (70)
M8011 2204EN
Summary of Contents for VSi 6-14
Page 1: ...M8011 2204EN 25 January 2022 Installation and operation manual VSi 6 14 VMi 6 17 ss Control...
Page 2: ......
Page 59: ...Dimensional drawings VSi 10VS14_2 VSI 1 ver 1 10VS14_2 VSI 2 ver 1 M8011 2204EN 57 70...
Page 60: ...Dimensional drawings VMi 10VMI141_2 VMI 1 ver 1 10VMI141_2 VMI 2 ver 1 58 70 M8011 2204EN...
Page 73: ......