4.6 Setting gas pressure regulator SKP
The operating area of the gas pressure regulator is determined by the spring installed
inside the pressure regulator. Spring operating area is described in the table below.
Springs can be ordered from Oilon Webshop.
SKP ver. 1
To change spring:
1. Remove the plug.
2. Remove the slot-head screw by turning counter-clockwise with a chisel-point
screwdriver.
3. Replace the spring.
Assemble in reverse order.
Do not overtighten the component’s screws. The component may
become damaged.
Spring type
pG ("W.C.)
∆p /
360
Color
Model
AGA29
≤ 8.8
2.2
blank
SKP25.0
AGA22
6.0 ... 48.2
11.9
yellow
SKP25.0
AGA23
40.2 ... 100.4
24.5
red
SKP25.0
AGA22
40.2 ... 281.0
-
yellow
SKP25.4
AGA23
≤ 602.8
245
red
SKP25.4
M4219 2305EN
39 (111)