Param. &
Display
RatioControl
Fuel settings
Special settings
Initial stage
Initialstage Gas
Initialstage Air
Initialstage Aux1
Initialstage Aux2
Initialstage Aux3
In standby position run servomotor´s axle between 2°- 88°. After maintenance check
servomotor´s proper function by running servomotor´s axle in these positions and
return servomotor to initial position.
6.6 Dismounting and changing servomotors
The permissible tightening torque for the elastic coupling clamping
screw is 2 Nm. The permissible tightening torque for the tightening
screw is 4 Nm.
Once the servomotor has been replaced, test that both the elastic
coupling and the servomotor's axle turn freely. Either monitor the
components during the next start-up or run the servomotor to its
standby position (initial stage).
98 (111)
M4219 2305EN
Summary of Contents for GP-600 M
Page 2: ......
Page 16: ...Block diagram of contact links Block diagram ver 7 14 111 M4219 2305EN...
Page 87: ...5 5 Time sequence diagram gas use 7550f57e 0515 Gp1 ver 6 M4219 2305EN 85 111...
Page 113: ...M4219 2305EN 111 111...
Page 114: ...112 111 M4219 2305EN...
Page 115: ......