4.4 Adjusting combustion differential air pressure switch
Combustion differential air pressure switch
The combustion differential air pressure switch monitors the pressure difference
generated by the burner fan.
LGW A2 ver. 2
Pos.
Item
A
Higher pressure
B
Lower pressure
C
Electrical connections
D
Adjustment wheel
1 and 2 Cross-head screw
If the pressure difference does not rise above the switch setting value, the burner will
shut down. The differential air pressure switch should be set to trigger before the CO
concentration in the flue gas exceeds 1 vol-% (10,000 ppm).